Chapter 4

4.1 Monitor Mode

4.1.1 Output frequency monitoring
When the output frequency monitoring function (d001) is selected, the inverter
displays the output frequency. The inverter displays "0.00" when the frequency
output is stopped.
The Hz monitor lamp lights up while the inverter is displaying the output frequency.
(Display)
0.00 to 99.99 in steps of 0.01 Hz
100.0 to 400.0 in steps of 0.1 Hz
Note: When you have selected the digital operator as the device to input frequency-setting commands (A001=02), you
can change the output frequency setting by using the
motor).
- The change in output frequency made in this mode can be reflected in the frequency setting (function "F001").
Press the STR key to write the new frequency over the currently selected frequency setting.
- You cannot change the output frequency while the PID function is enabled or the inverter is not operating the
motor.
4.1.2 Output current monitoring
When the output current monitoring function (d002) is selected, the inverter
displays the output current. The inverter displays "0.0" when the current output is
stopped.
The A monitor lamp lights up while the inverter is displaying the output current.
(Display)
0.0 to 999.9 in steps of 0.1 A
4.1.3 Rotation direction monitoring
When the rotation direction monitoring function (d003) is selected, the inverter
displays the motor operation direction.
The RUN lamp lights up while the inverter is operating the motor (in forward or reverse direction).
(Display)
F: Forward operation
o: Motor stopped
r: Reverse operation
4.1.4 Process variable (PV), PID feedback monitoring
When "01" (enabling PID operation) or "02" (enabling inverted-data output) has
been specified for function "A071" (PID Function Enable) and the process
variable (PV), PID feedback monitoring function (d004) is selected, the inverter
displays the PID feedback data.
You can also convert the PID feedback to gain data by setting a PV scale conversion (with function "A075").
Value displayed by function "d004" = "feedback quantity" (%) x " PV scale conversion (A075)"
The PV scale conversion can be set (by function "A075") within the range 0.01 to 99.99 in steps of 0.01.
(Display)
0.00 to 99.99 in steps of 0.01
100.0 to 999.9 in steps of 0.1
1000. to 9999. in steps of 1
100 to 999 in units of 10
Explanation of Functions
and/or
key (only while the inverter is operating the
4-1
Related code
d001: Output frequency monitoring
Related code
d002: Output current monitoring
Related code
d003: Rotation direction monitoring
Related code
d004: Process variable (PV),
PID feedback monitoring
A071: PID Function Enable
A075: PV scale conversion