Trane IntelliPak 1 Installation, Operation And Maintenance Manual page 76

Commercial packaged rooftop air conditioners with vav or szvav controls and eflex/ edrive
Table of Contents

Advertisement

U U n n i i t t S S t t a a r r t t u u p p
Figure 45. Supply fan performance with or without variable frequency drive - 40, 50 and 55 tons air-cooled, - forward
curved
8.0
1200 RPM
7.5
7.0
1100 RPM
6.5
6.0
1000 RPM
5.5
5.0
900 RPM
4.5
4.0
800 RPM
3.5
3.0
700 RPM
2.5
2.0
600 RPM
1.5
500 RPM
1.0
0.5
0.0
0
2000
4000
6000
I I m m p p o o r r t t a a n n t t : : Maximum static pressure leaving the
rooftop is 4.0" H
pressure drops from the supply fan to the
space cannot exceed 4.0" H
76
8000
10000
12000
14000
Airflow, CFM
O positive. The static
2
O.
2
16000
18000
20000
22000
N N o o t t e e s s : :
Fan performance for 40 and 50 to 55 ton
rooftops is identical. Contact your local
Trane ® representative for information on
oversized motors.
Shaded areas represent selectable area.
Contact your local Trane ® representative for
more information.
Supply fan performance curve includes
internal resistance of rooftop. For total static
pressure determination, system external
static must be added to appropriate
component static pressure drops
(evaporator coil, filters, optional economizer,
optional relief fan, optional heating system,
optional cooling only extended casing,
optional roof curb).
Maximum Cfm (for cULus approval) as
follows: 40 ton - 18,000 Cfm and 50 ton -
22,500 Cfm.
Minimum motor horsepower is 7.5 hp.
Maximum motor horsepower is 30 hp.
Maximum ½ hp to 15 hp fan Rpm is 1,141
Rpm, maximum 20 hp to 30 hp fan Rpm is
1,170 Rpm.
70%
80%
90%
24000
26000
RT-SVX072A-EN