Trane IntelliPak 1 Installation, Operation And Maintenance Manual page 150

Commercial packaged rooftop air conditioners with vav or szvav controls and eflex/ edrive
Table of Contents

Advertisement

S S e e r r v v i i c c e e a a n n d d M M a a i i n n t t e e n n a a n n c c e e
Table 72. Condenser fan VFD parameters
Descriptions
Menu
ID
Language
0-01
Regional Settings
0-03
Opera-
tion
Grid Type
0-06
display
[Hand on] - Key on
0-40
Motor Power (KW/HP)
1-20
Motor Voltage (V)
1-22
Motor Frequency (HZ)
1-23
Load
Motor Current (A)
1-24
and
motor
Motor Nominal Speed
1-25
Flying Start
1-73
Motor Thermal
1-90
Protection
DC Hold / Preheat
2-00
Current (%)
Brakes
DC Brake Current (%)
2-01
DC Brake Cut in Speed
2-04
Minimum Reference
3-02
Maximum Reference
3-03
3-15
Reference 1 Source
Refer-
ence /
3-16
Reference 2 Source
Ramps
3-17
Reference 3 Source
Ramp 1 Ramp up Time
3-41
Ramp 1 Ramp down
3-42
Time (S)
Motor Speed Low
4-12
Limit [HZ]
Motor Speed High
Limits /
4-14
Limit (Hz)
Warn-
ings
Current Limit (%)
4-18
Max Output
4-19
Frequency (Hz)
Terminal 18 Digital
5-10
Terminal 27 Digital
Digital
5-12
Terminal 29 Digital
5-13
150
Parameter Setting
[0] English US
[1] North American
Set to applicable unit power supply
[122] 440-480V/60Hz for 460V/60Hz units
[132] 525-600V/60Hz for 575V/60Hz units
For IT Grid (no ground connections) or Corner grounded Delta power supply systems, the
applicable voltage/Hz and IT-Grid or Delta should be selected.
[0] Disabled
LCP
Per Motor Nameplate KW- HP
Per Motor Nameplate Voltage
Per Motor Nameplate Frequency
Per Motor Nameplate FLA
Per Motor Nameplate RPM
(RPM)
[1] Enabled
[4] ETR Trip1
[0] 0%
[0] 0%
[10] 10 Hz
[6] 6Hz
(HZ)
[60] 60Hz
(HZ)
[11] Local bus reference
[0] No function
[0] No function
[10] 10s
(S)
[10] 10s
[6] 6Hz
[60] 60Hz
[100] 100% for 1HP Motor
[60] 60Hz
[0] No Operation
Input
[0] No Operation
Input
[0] No Operation
Input
RT-SVX072A-EN