Trane IntelliPak 1 Installation, Operation And Maintenance Manual page 145

Commercial packaged rooftop air conditioners with vav or szvav controls and eflex/ edrive
Table of Contents

Advertisement

Table 69. Supply fan VFD programming parameters
Description
Menu
ID
0-01
0-03
Operation
Display
0-06
[Hand on] - Key
0-40
Motor Power
1-20
Motor Voltage
1-22
Motor Frequency
1-23
Load and
Motor Current
Motor
1-24
Motor Nominal
1-25
Speed (RPM)
Flying Start
1-73
Motor Thermal
1-90
Preheat Current
2-00
Brakes
2-01
Current (%)
DC Brake Cut In
2-04
Speed (HZ)
3-02
Reference (HZ)
3-03
Reference (HZ)
Reference 1
3-15
Reference /
Reference 2
3-16
Ramps
Reference 3
3-17
Ramp 1 Ramp Up
3-41
Ramp 1 Ramp
3-42
Down Time (S)
RT-SVX072A-EN
Language
[0] English US
Regional
[1] North American
Settings
Set to applicable unit power supply
[102] 200-240V/60HZ for 208, and 230V/60HZ units
[122] 440-480V/60Hz for 460V/60Hz units
Grid Type
[132] 525-600V/60Hz for 575V/60Hz units
[12] 380-440V/50Hz for 380, and 415V/50Hz supply
For IT Grid (no ground connections) or Corner grounded Delta power supply systems, the
applicable voltage/Hz and IT-Grid or Delta should be selected.
[0] Disabled
on LCP
Per Motor Nameplate HP
[HP]
Per Motor Nameplate Voltage
(V)
Per Motor Nameplate Frequency
(HZ)
Per Motor Nameplate FLA
(A)
Per Motor Nameplate Rated Speed
[1] Enabled
[4] ETR Trip1
Protection
DC Hold /
[0] 0%
(%)
DC Brake
[0] 0%
[10] 10Hz
Minimum
Per Unit Nameplate - Evap Fan VFD Min Hz
Maximun
Per Unit Nameplate - Evap Fan VFD Max Hz
[11] Local bus reference
Source
[0] No function
Source
[0] No function
Source
[30] 30s
Time (S)
[30] 30s
S S e e r r v v i i c c e e a a n n d d M M a a i i n n t t e e n n a a n n c c e e
Parameter Setting
145