Specifications - Greenlee IPM-100 Instruction Manual

Industrial process control loop calibrator
Table of Contents

Advertisement

Available languages

Available languages

Specifications

Display: LCD
Polarity: Automatic
Ranges: 0.00 mA to 24.00 mA and –25.0% to 125.0% of 4 mA to 20 mA
Accuracy:
(0.08% of 24 mA span + 0.01 mA) = 0.03 mA
Temperature Effect: 0.01% per C between –2 C and 45 C
Warm-up Time: 10 seconds to specified accuracy; 2 minutes to maximum accuracy
Automatic Power-Off: After 30 minutes of inactivity
Overload Protection: 120 V AC/DC for 30 seconds
Operating Conditions: –20 C to 55 C (–4 F to 131 F), 10% to 90% relative humidity,
without condensation, for 24 hours
Indoor use only
Storage Conditions: –20 C to 55 C (–4 F to 131 F), 10% to 90% relative humidity, without
condensation, for 24 hours
Remove battery
Battery: Two 9-volt batteries (NEDA 1604, JIS 006P or IEC 6F22)
Source
Typical Drive Capability: 700
300
@ 20.00 mA with low batteries
Compliance Voltage: Nominal 14 VDC @ 20 mA with fresh batteries
Read
Voltage Burden: 0.9 VDC @ 4 mA, 1.2 VDC @ 20 mA, 1.9 VDC @ 24 mA excitation current
2-Wire Simulator
Loop Voltage Limits: 3 VDC minimum; 45 VDC maximum
Overload Protection: Current limited to 25 mA nominal
Power Transmitter
Typical Drive Capability: Same as for Source
Output Current: 0.00 mA to 24.00 mA
Compliance Voltage: Nominal 12 VDC @ 20 mA with fresh batteries
12
@ 20.00 mA with fresh batteries;