CJ1W-PNT21 PROFINET IO Controller Unit
Item
Memory Area Allocation CIO Area words allocated for the
FINS Messaging
FINS Services
Other functions
Protocol specifications
Item
PROFINET interface
Transfer specifications
PROFINET IO cable
PROFINET redundancy
Configuration
FINS service
CPU Bus Unit
DM Area words allocated for the
CPU Bus Unit
I/O data allocations
Reading IO Device Alarm
Reading and controlling the error
log
FINS/UDP
Error history size and storage
Memory Card backup function
/i
Protocol
PROFINET unit type
Isochronous mode
Alarms
Bitrate
Automatic detection of transmission speed
Type
Max transmission distance
Protocol
DTM
FINS/UDP
Specification
Fixed allocation of 25 words per Unit.
Start address: CIO 1500 + (25 * Unit number)
Not used
Maximum total size: 7168 words.
I/O Data can be allocated to up to 2 input and 2 output
areas.
Input and output areas can be mapped to CIO, DM, WR,
and HR areas, as well to EM banks. Mapping must be
defined through the configuration software.
The MEMORY AREA READ FINS command can be used to
obtain the last received IO Device Alarm message.
Catalogues the history of error events. The Unit supports
the following Error Log related FINS commands:
ERROR LOG READ
ERROR LOG CLEAR
Supported
Maximum packet size is 1500 bytes
The PROFINET IO Controller Unit supports storage of up to
80 error events, including time stamps, in volatile memory.
16 error events can be logged in non-volatile memory.
Allows PROFINET IO Controller Unit's Configuration to be
backed up as a file to a Memory Card in the CPU Unit.
The backed up configuration data can later be restored from
the Memory Card into the PROFINET IO Controller Unit.
Specification
PROFINET IO
PROFINET IO Controller
No
Yes, Alarm events from PROFINET IO Devices
are stored at and can be forwarded from the
CJ1W-PNT21
100 Mbps (100Base-TX)
No, fixed.
LAN cable according to PROFINET
specification.
100 m (distance between nodes)
PROFINET IO Controller Redundancy.
Included in CX-ConfiguratorFDT
Supported