Omron SYSMAC CS1W-ETN21 Operation Manual page 255

100base-tx ethernet units construction of networks
Hide thumbs Also See for SYSMAC CS1W-ETN21:
Table of Contents

Advertisement

Troubleshooting Procedures
Main code
Sub-code
22: Status
0F: Service in
error (operat-
progress, cannot
ing mode dis-
perform operation
agreement)
10: Socket not
open
11: Local node
busy, cannot
send
20
21
22
23
24
25
26: FINS/TCP not
connected
30: Connection
not establish
31: Connection
cannot be
changed
32: Service
stopped, cannot
perform operation
40: Incorrect
socket service
mode
23: Environ-
05: Parameter
ment error (no
error
such Unit)
07: Configuration
error
230
Check point
Socket status
The same socket service is
area
already in progress at the
specified socket number.
Socket status
The specified socket is not
area
open.
System load
The internal buffers are full
because there is too much traf-
fic at the local node, preventing
data from being sent.
Unit settings
The socket is not open for Sys-
tem Settings.
The socket is not open
because of the remote node
conversion command for the
FINS/TCP connection.
The socket is reopening
because the connection to the
remote node has closed.
The socket is reopening
because of a reception error.
The socket is reopening
because of a transmission
error.
The socket is reopening
because RST received in
response to keep-alive.
The socket is reopening
because of no keep-alive
response.
Command data
A connection is already estab-
lished with the specified
remote node.
Unit settings and
The specified connection num-
command data
ber is not set as a FINS/TCP
client in the Unit Setup.
Command data
While a remote node change
was being processed for the
specified connection number, a
request for a change was
received and the processing
was stopped.
High-speed
The high-speed option for the
option for socket
socket service was enabled in
service in Unit
the Unit settings, and the
settings
socket service was used with a
CMND(490) instruction.
Unit settings
IP address conversion failed.
IP address con-
IP address conversion is set for
version in Unit
automatic conversion only.
settings
Probable cause
Use the socket status flag in PC
memory to be sure that socket
service has finished before start-
ing services again.
Open the socket. For TCP sock-
ets, be sure to wait until connec-
tion is made.
Correct the user application to
reduce traffic at the Ethernet
Unit.
Correct the settings for the Unit
Setup, the FINS/TCP connection
number, the remote IP address,
and the remote port number.
Correct the settings for the FINS/
TCP connection number, the
remote IP address, and the
remote port number.
Correct the settings for the Unit
Setup, the FINS/TCP connection
number, the remote IP address,
and the remote port number.
Correct the settings for the FINS/
TCP connection number, the
remote IP address, and the
remote port number.
Disable the high-speed option or,
if it remains enabled, use the
socket service by manipulating
specific bits.
Check the IP address and subnet
mask in the System Setup and
be sure that settings are correct.
Check the mode settings in the
System Setup. This error will be
generated for the READ IP
ADDRESS TABLE command
only.
Section 8-4
Remedy