Omron SYSMAC CS1W-ETN21 Operation Manual page 235

100base-tx ethernet units construction of networks
Hide thumbs Also See for SYSMAC CS1W-ETN21:
Table of Contents

Advertisement

Error Log
Error
Meaning
code
03C2
FINS/TCP packet discarded
03C3
FINS/UDP packet discarded
210
Detailed error code
1st byte
2nd byte
01 to 10:
02:
Reopened
Connection
because
number
remote node
closed
03:
Reopened
because of
reception
error
04:
Reopened
because of
transmission
error
05:
Reopened
because RST
received from
remote node
06:
Reopened
because of
no keep-alive
response
07: Illegal
FINS/TCP
procedure
08: Insuffi-
cient mem-
ory during
server pro-
cessing
09: Insuffi-
cient mem-
ory during
client pro-
cessing
0A: Insuffi-
cient mem-
ory during
node switch-
ing
00
01 to FE:
Transmission
source node
address
Correction
Have the FINS/TCP connection
status checked when a
SEND(090), RECV(098), or
CMND(490) instruction is exe-
cuted in the ladder program.
Refer to Operation Manual, Con-
struction of Applications: SEC-
TION 7, and correct the remote
node (application on a personal
computer).
There is too much load (traffic) on
the Ethernet Unit. Correct the sys-
tem so that traffic is not concen-
trated.
The automatic generation (static)
method was used as the IP
address conversion method, so
remote IP address information in
internal memory could not be
changed.
Section 8-3
EE-
PROM
---
---
---
---

Advertisement

Table of Contents
loading

Table of Contents