Error Log
Error
Meaning
code
0300
Parameter error; packet discarded Commands
03C0
FINS/TCP setting error
03C1
Server setting error
Detailed error code
1st byte
2nd byte
Bit 15:
OFF
Bits 08 to 14: SNA
Bits 00 to 07: SA1
Responses
Bit 15:
ON
Bits 08 to 14: DNA
Bits 00 to 07: DA1
01 to 10:
01: Automati-
Connection
cally allo-
number
cated FINS
node address
duplication
02: Destina-
tion IP
address error
03: Destina-
tion port
number error
00: DNS
01: IP
01: SMTP
address
02: POP3
02: Host
03: SNTP
name
03: Port num-
ber
04: Other
parameters
Correction
Check the command format and
set the correct command data.
Refer to 1-5-1 FINS Communica-
tions Service in this manual and
the Operation Manual, Construc-
tion of Applications: SECTION 7
and set the FINS/TCP settings
correctly.
Set the server settings correctly
based on the information in the
detailed error code.
Section 8-3