Dm (Data Memory) Area; Operation; Timing Chart - Omron K3HB-PPB Technical Communications User's Manual

Digital indicators
Table of Contents

Advertisement

Programming Example 1: Connecting to a PLC
Pin
Signal name
number
28*
MIN
29*
HOLD
30*
RESET
31
POL
Note
1-5-2

DM (Data Memory) Area

IR 000
1-5-3

Operation

1-5-4

Timing Chart

D (START)
Upward differentiation of START signal
D (D.V)
Upward differentiation of DATA VALID signal
11-8
Signal
direction
Input
Minimum value output request
Input
HOLD input
Input
RESET input
Output
Data polarity signal
(1) I/O allocations marked with an asterisk are not used in this programming
example.
(2) The pin numbers shown in the above table are the pin numbers of the D-
sub connector on the special BCD output cable (sold separately).
Read data is stored in the memory, as shown below.
IR 000
In this programming example, IR 00113 in the CPU Unit of the PLC is turned
ON to read the measurement value of the Digital Indicator to the PLC and
store it in the DM area. No matter how long IR 00113 remains ON, data is
sampled only once.
RUN
START
KEEP
REQUEST
D.V.
Meaning
Output Unit, IR 0202*
Output Unit, IR 0203*
Output Unit, IR 0204*
Input Unit, IR 0107
IR 002
Polarity (bit 00)
10
10
10
10
10
Section 1-5
I/O allocation
4
digit (bits 00 to 03)
3
digit (bits 12 to 15)
2
digit (bits 08 to 11)
1
digit (bits 04 to 07)
0
digit (bits 00 to 03)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents