Attaching The Devicenet Communications Unit Connector - Omron K3HB-PPB Technical Communications User's Manual

Digital indicators
Table of Contents

Advertisement

DeviceNet Communications Cables Wiring
3-2-2

Attaching the DeviceNet Communications Unit Connector

5-6
Align the DeviceNet Communications Unit connector (marked with a C) with
the cable connector, and insert the cable connector fully into the DeviceNet
Communications Unit connector.
Tighten the set screws to a torque between 0.18 and 0.22 N·m to secure the
connector.
Align the connector with
the black wire at the top.
Use the following crimp terminals if using Thick DeviceNet Communications
Cables.
HR31-SC-111 (Hirose Electric)
Section 3-2
N
S
M
S