Commands and Responses (CompoWay/F Communications)

1-9-10 Write via Communications

Command
Response

1-9-11 Reset

Command
Response

1-9-12 Bank Selection

Command
1-18
Related
Command
MRC
SRC
code
information
"30"
"05"
"00"
Related information
"00"
Write via communications disabled
"01"
Write via communications enabled
This command is used to enable or disable "Write via communications." When
sent, it changes the set value of "Write via communications."
When write via communications is disabled, communications cannot be used
to write setting data or send operation commands.
The initial setting is "disabled."
This command can be used in both setting area 0 and setting area 1.
MRC
SRC
Response code
"30"
"05"
"0000"
Response codes: The above indicates a normal end. For the response codes,
see 1-7 Operation Commands (CompoWay/F Communications) (page 1-11).
Related
Command
MRC
SRC
code
information
"30"
"05"
"01"
Related information
"00"
Reset
This command resets the system to no-measurement status. It can only be
used in setting area 0.
MRC
SRC
Response code
"30"
"05"
"0000"
Response codes: The above indicates a normal end. For the response codes,
see 1-7 Operation Commands (CompoWay/F Communications) (page 1-11).
Command
Related
MRC
SRC
code
information
"30"
"05"
"02"
Related information
"00" to "07"
0 to 7
This command can be used only when "Bank Selection" is set to "Key."
This command is used to change between comparative set values preset in
banks. There are 8 banks numbered 0 to 7.
This command can be used in both setting area 0 and setting area 1.
Section 1-9
Description
Description
Bank No. selected