Mitsubishi Electric Mr. Slim PUHZ-ZRP35VKA Service Manual page 94

Split-type, heat pump air conditioners outdoor unit
Hide thumbs Also See for Mr. Slim PUHZ-ZRP35VKA:
Table of Contents

Advertisement

SW2 setting
Discharge superheat on error occurring
SHd
0 to 255
ON
Cooling = TH4−TH6
Heating = TH4−TH5
1
2 3 4 5 6
Sub cool on error occurring SC
0 to 130
ON
Cooling = TH6−TH3
Heating = TH5−TH2
1
2 3 4 5 6
Thermo-on time until error stops
0 to 999
ON
1
2 3 4 5 6
Indoor pipe temperature / Liquid
(TH2 (3))
ON
Indoor 3
−39 to 88
1
2 3 4 5 6
Indoor pipe temperature / Cond./ Eva.
(TH5 (3))
ON
Indoor 3
−39 to 88
1
2 3 4 5 6
Indoor pipe temperature / Liquid
(TH2 (4))
ON
Indoor 4
−39 to 88
1
2 3 4 5 6
Indoor pipe temperature / Cond. / Eva
(TH5 (4))
ON
Indoor 4
−39 to 88
1
2 3 4 5 6
OCH527C
Display detail
The black square ( ) indicates a switch position.
Explanation for display
0 to 255
(When the temperature is 100°C or more, hundreds
digit, tens digit and ones digit are displayed by
turns.)
(Example) When 150°C;
0.5 sec. 0.5sec. 2 sec.
0 to 130
(When the temperature is 100°C or more, hundreds
digit, tens digit and ones digit are displayed by
turns.)
(Example) When 115°C;
0.5 sec. 0.5sec. 2 sec.
0 to 999
(When it is 100 minutes or more, hundreds digit, tens
digit and ones digit are displayed by turns.)
(Example) When 415 minutes;
0.5 sec. 0.5sec. 2 sec.
−39 to 88
(When the temperature is 0°C or less, "–" and
temperature are displayed by turns.)
−39 to 88
(When the temperature is 0°C or less, "–" and
temperature are displayed by turns.)
When there is no indoor unit, "00" is displayed.
−39 to 88
(When the temperature is 0°C or less, "–" and
temperature are displayed by turns.)
−39 to 88
(When the temperature is 0°C or less, "–" and
temperature are displayed by turns.)
When there is no indoor unit, "00" is displayed.
94
1
50
1
15
4
15
Unit
:
:
Minute
:
:
:
: