Mitsubishi Electric Mr. Slim PUHZ-ZRP35VKA Service Manual page 92

Split-type, heat pump air conditioners outdoor unit
Hide thumbs Also See for Mr. Slim PUHZ-ZRP35VKA:
Table of Contents

Advertisement

SW2 setting
DC bus voltage
150 to 400 (ZRP35 to 140V)
ON
300 to 750 (ZRP100 to 140Y)
1
2 3 4 5 6
Capacity save
0 to 100
When air conditioner is connected to
M-NET and capacity save mode is
ON
demanded, a value from "0" to "100" is
displayed.
1
2 3 4 5 6
When there is no setting
of capacity save, "100" is
displayed.
Error postponement code history (2)
of outdoor unit
ON
1
2 3 4 5 6
Error postponement code history (3)
of outdoor unit
ON
1
2 3 4 5 6
Error history (3) (Oldest)
ON
Alternate display of abnormal unit
number and code.
1
2 3 4 5 6
Error thermistor display
ON
When there is no error thermistor,
"–" is displayed.
1
2 3 4 5 6
Operation frequency on error occurring
0 to 255
ON
1
2 3 4 5 6
Fan step on error occurring
0 to 10
ON
1
2 3 4 5 6
Outdoor pipe temperature(TH33)
ON
−39 to 88
1
2 3 4 5 6
OCH527C
Display detail
The black square ( ) indicates a switch position.
Explanation for display
150 to 400 (RP35 to 140V)
300 to 750 (RP100 to 140Y)
(When it is 100V or more, hundreds digit, tens
digit and ones digit are displayed by turns.)
0 to 100
(When the capacity is 100% hundreds digit, tens digit
and ones digit are displayed by turns.)
(Example) When 100%;
0.5 sec. 0.5sec. 2 sec.
Postponement code display
Blinking: During postponement
Lighting: Cancellation of postponement
"00" is displayed in case of no postponement.
Postponement code display
Blinking: During postponement
Lighting: Cancellation of postponement
"00" is displayed in case of no postponement.
When no error history, "0" and "– –" are displayed by
turns.
3: Outdoor pipe temperature /Liquid (TH3)
6: Outdoor pipe temperature /2-phase (TH6)
7: Outdoor outside temperature (TH7)
8: Outdoor heatsink (TH8)
0 to 255
(When it is 100 Hz or more, hundreds digit, tens digit
and ones digit are displayed by turns.)
(Example) When 125 Hz;
0.5 sec. 0.5sec. 2 sec.
0 to 10
−39 to 88
(When the temperature is 0: or less, "–" and
temperature are displayed by turns.)
92
1
00
1
25
Unit
V
%
Code
display
Code
display
Code
display
Code
display
Hz
Step
°C

Advertisement

Table of Contents
loading

Table of Contents