DATA
6-1. REFILLING REFRIGERANT CHARGE (R410A: kg) PUHZ-ZRP35-140
Service Ref.
PUHZ-ZRP35VKA
PUHZ-ZRP35VKAR1
PUHZ-ZRP35VKAR1-ER
PUHZ-ZRP35VKAR1-ET
PUHZ-ZRP50VKA
PUHZ-ZRP50VKAR1
PUHZ-ZRP50VKAR1-ER
PUHZ-ZRP50VKAR1-ET
PUHZ-ZRP60VHA
PUHZ-ZRP60VHAR1
PUHZ-ZRP60VHAR1-ER
PUHZ-ZRP60VHAR1-ET
PUHZ-ZRP71VHA
PUHZ-ZRP71VHAR1
PUHZ-ZRP71VHAR1-ER
PUHZ-ZRP71VHAR1-ET
PUHZ-ZRP100VKA
PUHZ-ZRP100YKA
PUHZ-ZRP100YKAR1
PUHZ-ZRP125VKA
PUHZ-ZRP125YKA
PUHZ-ZRP125YKAR1
PUHZ-ZRP140VKA
PUHZ-ZRP140YKA
PUHZ-ZRP140YKAR1
6-2. COMPRESSOR TECHNICAL DATA
PUHZ-ZRP35VKAR1
Service Ref.
PUHZ-ZRP35VKAR1-ER
PUHZ-ZRP35VKAR1-ET
Compressor model
U-V
Winding
U-W
Resistance
( " )
W-V
Service Ref.
PUHZ-ZRP71VHA -ER
PUHZ-ZRP71VHA -ET
Compressor model
U-V
Winding
U-W
Resistance
( " )
W-V
OCH527C
10 m
20 m
1.8
2.0
2.0
2.2
3.1
3.3
3.1
3.3
4.6
4.8
4.6
4.8
4.6
4.8
PUHZ-ZRP35VKA
SNB092FGCM
0.64
0.64
0.64
PUHZ-ZRP71VHA
PUHZ-ZRP71VHA R1
SNB172FSHM1
1.34
1.34
1.34
Piping length (one way)
30 m
40 m
50 m
2.2
2.4
2.6
2.4
2.6
2.8
3.5
4.1
4.7
3.5
4.1
4.7
5.0
5.6
6.2
5.0
5.6
6.2
5.0
5.6
6.2
Additional charge is required for pipes longer
than 30 m.
PUHZ-ZRP50VKA
PUHZ-ZRP50VKAR1
PUHZ-ZRP50VKAR1-ER
PUHZ-ZRP50VKAR1-ET
SNB130FGCM2
0.64
0.64
0.64
PUHZ-ZRP100/125/140VKA
ANB33FNFMT
0.466
0.466
0.466
10
60 m
75 m
6.8
7.4
6.8
7.4
6.8
7.4
(at 20°C)
PUHZ-ZRP60VHA
PUHZ-ZRP60VHAR1
PUHZ-ZRP60VHA R1-ER
PUHZ-ZRP60VHA R1-ET
SNB130FGCM1
0.64
0.64
0.64
(at 20°C)
PUHZ-ZRP100/125/140YKA
PUHZ-ZRP100/125/140YKAR1
ANB33FNCMT
1.20
1.20
1.20
Initial
charged
2.2
2.4
3.5
3.5
5.0
5.0
5.0