Mitsubishi Electric Mr. Slim PUHZ-ZRP35VKA Service Manual page 65

Split-type, heat pump air conditioners outdoor unit
Hide thumbs Also See for Mr. Slim PUHZ-ZRP35VKA:
Table of Contents

Advertisement

Check method of DC fan motor (fan motor / outdoor controller circuit board)
Notes
1
· High voltage is applied to the connecter (CNF1, 2) for the fan motor. Pay attention to the service.
· Do not pull out the connector (CNF1, 2) for the motor with the power supply on.
(It causes trouble of the outdoor controller circuit
Self check
2
Symptom : The outdoor fan cannot turn around.
Fuse check
Check the fuse (F5) on outdoor
controller board.
Did the fuse blow?
No
Wiring contact check
Contact of fan motor connector (CNF1, 2)
Is there contact failure?
No
Power supply check (Remove the connector (CNF1, 2))
Measure the voltage in the outdoor controller circuit
TEST POINT
1 : V
(between 1 (+) and 4 (-) of the fan connector): V
DC
TEST POINT
2 : V
(between 5 (+) and 4 (-) of the fan connector): V
CC
Is the voltage normal?
No
Replace outdoor
controller board.
Check the operation.
NG
Replace the fan motor.
OCH527C
board and fan motor.)
Replace outdoor controller board (C.B)
Yes
and fan motor (MF1, 2).
Recover wiring.
Yes
board.
Replace the fan motor.
Yes
Check the operation of fan.
Replace outdoor controller board.
OK
END
65
250–330 V DC
DC
15 V DC
CC
Yes
OK
NG
END