TECHNICAL DATASHEET
Force-GT DIN Rail Power Supply
24 V 960 W 3 Phase / DRF-24V960W3GBA
Protections
Overvoltage
Overload / Overcurrent
Over Temperature
Short Circuit
Internal Fuse
Degree of Protection
Protection Against Shock
*6 Constant current limit protection for inductive and capacitive load applications
*7 PE: Primary Earth
Reliability Data
MTBF
Expected Cap Life Time
Safety Standards / Directives
Electrical Equipment of Machines
Electrical Equipment for Use in Electrical Power Installations
Safety Entry Low Voltage
Electrical Safety
Electrical Equipment for Measurement,
Control, and Laboratory Use
CE
UKCA
Galvanic Isolation
All parameters are specified at 25°C ambient and AC input 3x unless otherwise indicated.
4
www.DeltaPSU.com (May 2022, Rev. 00)
< 35 V, Hiccup Mode, Non-Latching (Auto-Recovery)
110 – 150% of rated load current, Auto-recovery
Continuous current limit Mode*
60°C-80°C Surrounding Air Temperature @ 100% load,
Non-Latching (Auto-Recovery)
Hiccup Mode, Non-Latching
(Auto-Recovery when the fault is removed)
T 4 A
IP20
Class I with PE
Telcordia SR-332
> 500,000 hrs.
I/P: 3 x 400 Vac & 3 x 500 Vac, O/P: 100% load, Ta: 25°C
10 Years
I/P: 3 x 400 Vac & 3 x 500 Vac, O/P: 24 V, 20 A, Ta: 40°C
EN/BS EN 60204-1 (over voltage category III)
IEC/EN/BS EN 62477-1 / IEC 62103
SELV (IEC 60950-1)
SIQ Bauart
EN 62368-1, EN 61010-1, EN 61010-2-201, EN 62477-1
UL/cUL recognized
UL 62368-1 and CSA C22.2 No. 62368-1 (File No. E191395)
CB scheme
IEC 60950-1, IEC 62368-1, IEC 61010-1, IEC 61010-2-201
UKCA
BS EN 62368-1, BS EN 61010-1, BS EN 61010-2-201
UL/cUL listed
UL 61010-1, UL 61010-2-201
In conformance with EMC Directive 2014/30/EU and Low
Voltage Directive 2014/35/EU
In conformance with Electrical Equipment (Safety) Regulations
2016 No. 1011 and
The Electromagnetic Compatibility Regulations 2016 No. 1091
Input to Output
4.0 kVac
Input to Ground
2.0 kVac
Output to Ground
1.5 kVac
DC OK relay contact to
0.5 kVac
Output
DC OK relay contact to
1.5 kVac
Ground
6
(Vo > 80%)
*7