TECHNICAL DATASHEET
Force-GT DIN Rail Power Supply
24 V 960 W 3 Phase / DRF-24V960W3GBA
Mechanical
Case Cover / Chassis
Dimensions (H x W x D)
Unit Weight
Indicator
Cooling System
Terminal*
5
Wire
Mounting Rail
Noise (1 Meter from power supply)
*5 The torque at the input terminal connector shall not exceed 5.4 Kgf.cm. (4.7 lbf.in). The torque at the output terminal connector shall not exceed 19.7 Kgf.cm. (17.1 lbf.in).
Environment
Surrounding Air Temperature
Power De-rating
Operating Humidity
Operating Altitude and
Over Voltage Category
Shock Test
Vibration
Pollution Degree
All parameters are specified at 25°C ambient and AC input 3x unless otherwise indicated.
3
www.DeltaPSU.com (May 2022, Rev. 00)
Aluminum
124 x 110 x 128.7 mm (4.88 x 4.33 x 5.07 inch)
2.26 kg (4.98 lb)
Green LED
DC OK
Convection
Input
4 Pins (Rated 600 V / 30 A)
4 Pins (Rated 300 V / 65 A)
Output
2 Pins (Rated 300 V / 12 A)
Signal
Input
AWG 18-10
Output
AWG 12-6
AWG 20-16
Signal
Standard TS35 DIN Rail in accordance with EN 60715
Sound Pressure Level (SPL) < 25dBA
3-Phase
Operating
-25°C to +70°C (-40°C Cold Start)
2-Phase
-25°C to +60°C (-40°C Cold Start)
Storage
-40°C to +85°C
> 55°C de-rate power by 3.33% / °C
Vertical Mounting
> 25°C de-rate power by 2.5% / °C
Horizontal Mounting
2-Phase
Input Voltage
2 x 340-575 Vac de-rate power to 80%
5 to 95% RH (Non-Condensing)
OVC III
0 to 2,500 Meters (8,200 ft.)
OVC II
2,500 to 6,000 Meters
(19,680 ft.)
0 to 5,000 Meters (16,400 ft.)
Non-Operating
IEC 60068-2-27, Half Sine Wave: 50 G for duration of 11 ms;
3 times per direction
Operating
IEC 60068-2-6, Sine Wave: 10-500 Hz; 3G peak;
60 min per axis for all X, Y, Z directions
2
According to IEC/EN 62477-1 /
EN 60204-1 (clearance and
creepage distances) and IEC
62103 (safety part)
According to IEC/EN 62368-1,
IEC/EN 61010