Test & Sw2 Buttons; Memory Card; Factory Superheat Setting; Superheat Offset Dip Switch Settings - Rheem P17 Series Installation Instructions Manual

Three stage r-410a heat pump outdoor units
Table of Contents

Advertisement

7.7 EcoNet
7.7.2 TEST and SW2 Buttons
TEST and SW2 buttons are used to enter the
following menus and modes:
Test mode
Forced Defrost
Fault Code Recall Menu
Compressor Speed Menu
Superheat Menu
Outdoor  Unit  
(-­‐)P1724  
(-­‐)P1736  
(-­‐)P1748  

7.7.5 Superheat Offset DIP Switch Settings

(-­‐)P1760  
(DIP Switch Bank on the Right)
Although the factory programmed superheat setting
is considered to be the most efficient setting for
each unit, installation conditions can effect the
measurement of superheat on the VSODC. For this
 
Superheat  
Off  Set  from  
Offset  Selection  
Programmed  
Profile  
Setting  (°F)  
A  
B  
C  
D  
 
 
7.7.6 Defrost Termination Temperature DIP Switches
(DIP Switch Bank on the Left)
Off
Off
Off
On
On
Off
On
On
7.0 COMPONENTS & CONTROLS
Variable Speed Outdoor Control (VSODC) (cont.)
Superheat  
(°F)  
6  
6  
6  
8  
0  
-­‐4  
-­‐2  
+2  
60
F [15.6
C]
º
º
50
F [10
C]
º
º
40
F [4.4
C]
º
º
70
F [21.1
C]
º
º

7.7.3 Memory Card

• The memory card stores all unit information.
• The unit information is called model data.
• The model data is all the information needed for
proper unit operation of that specific model.

7.7.4 Factory Superheat Setting

Dipswitch  Settings  
1  
The VSODC is pre-programmed with the optimum
Off  
superheat setting of 6º for each outdoor unit.
Off  
Off  
Off  
reason the following dip switch settings have been
provided to enable flexibility for various installation
conditions.
2  
Off  
Off  
Off  
Off  
35