Installation Space Examples
• The installation space requirement shown in the following figure is
a reference for cooling operation when the outdoor temperature is
32°C.
If the design outdoor temperature exceeds 32°C or the heat load
exceeds maximum capacity in all the outdoor unit, take an even
large space on the intake shown in the following figure.
• During installation, install the units using the most appropriate of
the patterns shown in the following figure for the location in
question, taking into consideration human traffic and wind.
• If the number of units installed is more than that shown in the
pattern in the following figure, install the units so there are no short
circuits.
• As regards space in front of the unit, consider the space needed for
the local refrigerant piping when installing the units.
• If the work conditions in the following figure do not apply, contact
your dealer or Daikin directly.
Note
The black arrow indicates the suction side of the outdoor units.
b
a
A
d
b
a
e
A
d
a
A
a
A
A+B+C+D
a≥50
1
b≥300
c≥50
d≥500
LREQ15+20B7Y1R
Air cooled refrigeration condensing unit
4P360438-1B – 2014.01
1
B
c
C
D
B
e
e
D
3
B
b
e
c
C
f
d
D
4
B
b
e
c
f
C
d
D
A+B
a≥100
a≥200
b≥100
b≥300
c≥100
d≥500
a≥50
b≥300
2
c≥50
d≥500
e≥200
a≥50
b≥300
3
c≥50
d≥500
e≥200
f≥600
a≥50
b≥300
4
c≥50
d≥300
e≥200
f≥500
NOTE) For patterns 1 and 2
• Wall height for front side no higher than 1500 mm.
• Wall height on the suction side no higher than 500 mm.
• Wall height for sides – no limit
• Make sure each unit is installed level.
• Install the slave unit adjacent to the master unit.
• Make sure the slave unit faces the same direction as the master
unit.
2
• Provide enough space for maintaining and servicing the units.
• Provide adequate space for the air in- and outlets.
• Make sure the total length of the gas piping between the
outdoor unit and the outdoor unit multi-connection piping kit is
c
C
≤10 m.
• If the height is exceeded the above, calculate h1 and h2 shown
in the figure below, and add h1/2 to the service space of front
side and h2/2 to the service space of suction side.
h
2
h
1
h
2
1
h
h
2
2
2
CAUTION
Branch switch,
overcurrent breaker
(Earth leakage breaker)
Showcase
A+B+C+D
a≥100
b≥100
c≥100
d≥500
e≥300
A+B+C+D
a≥100
b≥100
c≥100
d≥500
e≥300
f≥500
A+B+C+D
a≥100
b≥100
c≥100
d≥100
e≥300
f≥500
h
1
Control panel
Warning panel
Branch switch,
overcurrent breaker
(Earth leakage breaker)
A+B
a≥200
b≥300
e≥400
A+B
A+B
(mm)
Installation manual
4