Fuel Conversion / Gas Connections

Fuel Consumption

Generator
15 kw EcoGen
3
* Natural gas is in m
/h / ft
** Propane is in gal/h / l/h (LP) / ft
*** Values given are approximate
These are approximate values. Use the appropriate spec sheet or owner's manual for specific values.
Verify that gas meter is capable of providing enough fuel flow to include household appliances and all other loads.
NOTE: The gas supply and pipe MUST be sized at 100% load BTU / Megajoule rating.
Always refer to the owner's manual for the proper BTU, Megajoule and required gas pressures:
– Natural Gas:
3
BTU = ft
/h x 1000
Megajoules = m
– Liquid Propane Vapor:
3
BTU = ft
/h x 2500
Megajoules = m

Fuel Line Sizing

Selecting the correct size fuel line is crucial to the proper
operation of the unit.
IMPORTANT NOTE: The generator inlet size does not
dictate the size of gas pipe to be used!
For further information refer to NFPA 54 for NG, or NFPA
58 or ICC IFGC for LP.
Measure the distance from the generator to the gas
source.
IMPORTANT NOTE: The generator should be plumbed
directly from the source, not off the end of an existing low
pressure system.
18
Natural Gas
1/2 Load
Full Load
4.25 / 150
8.16 / 288
3
/h
3
/h (LPV)
3
/h x 37.26
3
/h / hour x 93.15
Propane
1/2 Load
1.48 / 5.62 / 54.00
Installation Guidelines For 60 Hz EcoGen™ Generators
Full Load
2.86 / 10.82 / 104.00