installation
MINIMUM RECOMMENDED FLUE HEIGHTS IN FEET
ELEVATION (FT)
ABOVE SEA LEVEL
0-1000
1000-2000
2000-3000
3000-4000
4000-5000
5000-6000
6000-7000
7000-8000
8000-9000
9000-10000
NOTE: No more than two offsets (four elbows) allowed. Two 45

Recommended Heights For Woodstove Flue

Simple rules on draft. See Table 1.
1) At sea level minimum height is 12' straight.
2) Add the following vertical height to compensate for:
45 deg. elbow
= 1 ft.
90 deg. elbow
= 2 ft.
"T"
Each foot of horizontal run = 2 ft.
3) Add 4% overall for each 1000' above sea level.
Example: a)
1-1/2 ft. of horizontal run
one "T"
Total Addition (at sea level)
Example: b)
One 90 deg. elbow
2 ft. of horizontal run
one "T"
Total Addition (at sea level)
Elevation
Example a)
0'
18'
1000'
18.72'
2000'
19.44'
5000'
21.60'
8000'
23.76'
WARNING:
DO NOT INSTALL IN SLEEPING
ROOM
|
18
F2450M Regency Freestanding Woodstove
TABLE 1
(Measured from the top of the unit)
0
2 x 15
12.0
13.0
12.5
13.5
13.0
14.0
13.5
14.5
14.0
15.0
14.5
15.5
15.0
16.0
15.5
16.5
16.0
17.0
16.5
17.5
= 3 ft.
= 3 ft.
= 3 ft.
= 6 ft.
= 2 ft.
= 4 ft.
= 3 ft.
= 9 ft.
Recommended Flue Height
Example b)
21'
21.84'
22.68'
25.20'
27.72'
CAUTION: The structural integrity of the mobile home
floor, wall and ceiling/roof must be maintained.
# OF ELBOWS
4 x 15
2 x 30
o
o
o
14.0
15.0
18.0
14.5
15.5
19.0
15.0
16.0
19.5
15.5
17.0
20.0
16.0
17.5
21.0
17.0
18.0
21.5
17.5
18.5
22.5
18.0
19.0
23.0
18.5
20.0
24.0
19.0
20.5
24.5
elbows equal one 90
o
4 x 30
2 x 45
4 x 45
o
o
o
16.0
20.0
16.5
21.0
17.0
21.5
18.0
22.5
18.5
23.0
19.0
24.0
20.0
25.0
20.5
25.5
21.0
26.5
22.0
27.0
elbow.
o
Draft is the force which moves air from the appliance
up through the chimney. The amount of draft in your
chimney depends on the length of the chimney, local
geography, nearby obstructions and other factors.
Too much draft may cause excessive temperatures
in the appliance and may cause damage. An un-
controllable burn or excessive temperature indicates
excessive draft. Inadequate draft may cause back
puffing into the room and plugging of the chimney.
Inadequate draft will cause the appliance to leak
smoke into the room through appliance and chim-
ney connector joints. Ensure the heater is installed
in areas that are not too close to neighbors or in
valleys that would cause unhealthy air quality or
nuisance conditions.