Gas Supply - Biasi M300V.2025 SM User Manual And Installation Instructions

Combi
Table of Contents

Advertisement

Symbol Location position
A *
Directly below an opening, air brick, opening window, etc.
B *
Above an opening, air brick, opening window, etc.
C *
Horizontally to an opening, air brick, opening window, etc.
Below temperature-sensitive building components, e.g.
D **
plastic gutter soil pipes or drain pipes
E **
Below eaves
F
Below balconies
G
From a vertical drain pipe or soil pipe
H ***
From an internal or external corner
I
Above ground, roof or balcony level
J
From a surface facing a terminal
K
From a terminal facing a terminal
From an opening in the car-port (e.g. door, window) into
L
the dwelling
M
Vertically from a terminal on the same wall
N
Horizontally from a terminal on the same wall
O
From the wall on which the terminal is mounted
P
From a vertical structure on the roof
Q
Above intersection with the roof
R
From a roof window and terminal
S
From a roof window and terminal
*
In addition, for temperature and structural reasons, the terminal should not be near than 150
mm to an opening in the building fabric formed for the purpose of accommodating a built-in
element such as a sealed window frame.
**
A heat protection shield should also be installed.
*** The reference to external corners does not apply to building protrusions not exceeding 450
mm, such as disused chimneys on external walls.
5.4

Gas supply

The Gas meter is connected to the service pipe by the local gas region or a local gas region
contractor.
If the gas supply for the boiler serves other appliances ensure that an adequate supply is avail-
able both to the boiler and the other appliance when they are in use at the same time.
Pipework must be of adequate size. Pipes of a smaller size than the boiler inlet connection should
not be used.
Installation pipes should be fitted in accordance with BS 6891 and the complete installation
should be tested for tightness.
For Ireland (IE), refer to I.S.813.2002.
- 42 -
- 42 -
GENERAL REQUIREMENTS
Minimum dimensions
(mm)
300
300
300
75
200
200
150
300
300
600
1 200
Not recommended
1 500
300
Please refer to the flue
assembly instructions
600
600
600
2 500