Products Solutions Services BA02215F/00/EN/01.21-00 71548521 2022-02-28 Valid as of version 01.00.zz (Device firmware) Operating Instructions Liquiphant FTL64 Vibronic HART Point level switch for liquids in high-temperature applications...
Page 2
Liquiphant FTL64 HART Order code: XXXXX-XXXXXX Ser. no.: XXXXXXXXXXXX Ext. ord. cd.: XXX.XXXX.XX Serial number www.endress.com/deviceviewer Endress+Hauser Operations App A0023555 Endress+Hauser...
Liquiphant FTL64 HART Table of contents Table of contents About this document ....6 Electrical connection ....20 Purpose of this document .
Page 4
Table of contents Liquiphant FTL64 HART 9.4.2 FieldCare/DeviceCare via service 11.8.2 Resetting the device via operating interface (CDI) ....keys on the electronic insert ..
Page 5
Liquiphant FTL64 HART Table of contents 15.3.11 Electromagnetic compatibility (EMC) ......59 15.4 Process ......59 15.4.1 Process temperature range .
About this document Liquiphant FTL64 HART About this document Purpose of this document These Operating Instructions contain all the information that is required in the various phases of the life cycle of the device: from product identification, incoming acceptance and storage, to mounting, connection, operation and commissioning through to troubleshooting, maintenance and disposal.
Registered trademark of the FieldComm Group, Austin, Texas, USA Bluetooth® The Bluetooth® word mark and logos are registered trademarks owned by the Bluetooth SIG, Inc. and any use of such marks by Endress+Hauser is under license. Other trademarks and trade names are those of their respective owners. Apple®...
It meets the general safety standards and legal requirements. It also complies with the EU directives listed in the device-specific EU Declaration of Conformity. Endress+Hauser confirms this by affixing the CE mark to the device. Endress+Hauser...
Liquiphant FTL64 HART Product description Functional Safety SIL (optional) The Functional Safety Manual must be strictly observed for devices that are used in functional safety applications. IT security We only provide a warranty if the device is installed and used as described in the Operating Instructions.
Incoming acceptance and product identification Liquiphant FTL64 HART Product design A0042420 1 Product design Housing with electronic insert and cover Temperature spacer with gas-tight glass feedthrough → 2 lengths available, depending on the process temperature Process connection (flange or thread)
All of the information on the measuring device is displayed along with an overview of the scope of technical documentation provided. • Enter the serial number on the nameplate into the Endress+Hauser Operations app or scan the 2-D matrix code on the nameplate with the Endress+Hauser Operations app 4.2.1...
Mounting Liquiphant FTL64 HART A0042422 2 Handling the device during transportation Mounting Mounting instructions • Any orientation for device with short pipe up to approx. 500 mm (19.7 in) • Vertical orientation from above for device with long pipe •...
Liquiphant FTL64 HART Mounting 5.1.1 Pay attention to the temperature for devices with a PFA coating (conductive) The difference in temperature between the outer and inner side of the flange may not exceed 60 °C (140 °F). If necessary, use external insulation.
Mounting Liquiphant FTL64 HART > 25 (0.98) A0042333 6 Installation example for low-viscosity liquids. Unit of measurement mm (in) High viscosity NOTICE Highly viscous liquids may cause switching delays. ‣ Make sure that the liquid can run off the tuning fork easily.
Liquiphant FTL64 HART Mounting A0042345 8 Installation examples for a highly viscous process medium 5.1.5 Take clearance into consideration Allow sufficient space outside the tank for mounting, connection and settings involving the electronic insert. A0042340 9 Take clearance into consideration 5.1.6...
Mounting Liquiphant FTL64 HART A0042356 10 Examples of support in the event of dynamic load Marine approval: In the case of pipe extensions or sensors longer than 1 600 mm, a support is needed at least every 1 600 mm.
Page 17
Liquiphant FTL64 HART Mounting Installing in pipes • Flow velocity up to 5 m/s with a viscosity of 1 mPa⋅s and density of 1 g/cm (SGU). Check for correct functioning in the event of other process medium conditions. • The flow will not be significantly impeded if the tuning fork is correctly aligned and the marking is pointing in the direction of flow.
Page 18
Mounting Liquiphant FTL64 HART Aligning the cable entry 4 3.5 Nm A0042355 14 Housing with external locking screw and drip loop The locking screw is not tightened when the device is delivered. 1. Loosen the external locking screw (maximum 1.5 turns).
Liquiphant FTL64 HART Mounting Turning the display module WARNING Supply voltage switched on! Risk of electric shock and/or explosion! ‣ Switch off the supply voltage before opening the device. 4 0.7 Nm A0038224 1. If fitted: release the screw of the cover lock for the electronics compartment cover using the Allen key.
Electrical connection Liquiphant FTL64 HART Electrical connection Required tool • Screwdriver for electrical connection • Allen key for screw of cover lock Connecting requirements 6.2.1 Cover with securing screw In the case of devices for use in the hazardous area with a certain type of protection, the cover is sealed by a securing screw.
Liquiphant FTL64 HART Electrical connection Connecting the device A0046355 Connection compartment cover Housing thread The thread of the electronics and connection compartment is coated with lubricant varnish. Avoid additional lubrication. 6.3.1 Supply voltage • U = 10.5 to 35 V (Ex d, Ex e, non-Ex) •...
6.3.5 Overvoltage protection Devices without optional overvoltage protection Equipment from Endress+Hauser fulfills the requirements of the product standard IEC/DIN EN 61326-1 (Table 2 Industrial Environment). Depending on the type of port (DC supply, input/output port) different test levels according to IEC/DIN EN 61326-1 against transient overvoltages (Surge) are applied...
Liquiphant FTL64 HART Electrical connection 6.3.6 Wiring WARNING Supply voltage might be connected! Risk of electric shock and/or explosion! ‣ If the device is used in hazardous areas, make sure to comply with national standards and the specifications in the Safety Instructions (XAs). The specified cable gland must be used.
Liquiphant FTL64 HART Electrical connection M12 plug A0011175 19 M12 plug, pin assignment Signal + Not assigned Signal – Ground For more details, see the "Accessories" section. Ensuring the degree of protection 6.4.1 Degree of protection In accordance with DIN EN 60529, NEMA 250 IP66/IP68 NEMA 4X/6P (1.83 m H...
• Operation via optical operating keys on the device display (optional) • Operation via Bluetooth® wireless technology (with optional device display with Bluetooth) with Smartblue app or FieldXpert, DeviceCare • Operation via operating tool (Endress+Hauser FieldCare/DeviceCare, handheld terminal, AMS, PDM, ...) 4 to 20 mA HART (FEL60H) electronic insert...
Liquiphant FTL64 HART Operation options Function test using operating key on electronic insert Display A0046571 21 Operating keys on the electronic insert Operating key for reset password Operating key for proof test (> 3 s) When performing the proof test in safety instrumented systems according to SIL or WHG: comply with the instructions in the Safety Manual.
Structure and function of the operating menu The differences between the structure of the operating menus of the local display and the Endress+Hauser FieldCare or DeviceCare operating tools can be summarized as follows: The local display is suitable for configuring simple applications.
Prerequisite • Device with device display including Bluetooth • Smartphone or tablet with Endress+Hauser SmartBlue app or PC with DeviceCare from version 1.07.05 or FieldXpert SMT70 The connection has a range of up to 25 m (82 ft). The range can vary depending on environmental conditions such as attachments, walls or ceilings.
Access via the operating tool is possible: • Via HART communication, e.g. Commubox FXA195 • Via Endress+Hauser Commubox FXA291 With the Commubox FXA291, a CDI connection can be established with the device interface and a Windows PC/notebook with a USB port...
Liquiphant FTL64 HART Commissioning Device variable Measured value Tertiary variable (TV) parameter (Third variable) Fork state Quaternary variable (QV) parameter (Quaternary variable) Sensor temperature Primary variable (PV) parameter is always applied to the current output. Level limit detection is the initial state depending on the fork state (uncovered/covered) and the safety...
Commissioning Liquiphant FTL64 HART 9.1.1 As-delivered state If no customized settings were ordered: • Assign PV parameter Level limit detection (8/16 mA mode) • MAX safety mode • Alarm condition set to min. 3.6 mA • DIP switch for locking in OFF position •...
A0039148 Computer with FieldCare/DeviceCare operating tool Commubox FXA291 Service interface (CDI) of the device (= Endress+Hauser Common Data Interface) At least 22 mA is required to update (flash) the device firmware. Configuring the device address via software See HART address parameter.
Commissioning Liquiphant FTL64 HART A0046404 Click "Settings" and select the desired language: A0046406 Setting the language for the local display via DeviceCare Navigation: System → Display → Language ‣ Set the desired language in the Language parameter. Device configuration 9.7.1...
In the Simulation submenu the user can simulate with the options Fork state (uncovered/ covered), Sensor frequency, Current output and Diagnostic event simulation. DeviceCare is available for download at www.software-products.endress.com. You must register in the Endress+Hauser software portal to download the product.
Commissioning Liquiphant FTL64 HART Navigation: Diagnostics → Simulation → Simulation Protecting settings from unauthorized access 9.9.1 Locking or unlocking the hardware Display A0046569 25 Functions of the DIP switches on the electronic insert DIP switch for safety function, software-defined (SW, default=MAX) or set permanently to MIN DIP switch for locking and unlocking the device (hardware) DIP switch (2) on the electronic insert is used to lock or unlock operation.
Liquiphant FTL64 HART Operation Parameter configuration (Operator user role): Parameter configuration of the device is locked in the Operator user role. Unlocking access: Access to parameter configuration can be unlocked by entering the password. The user role changes back to Maintenance.
The Heartbeat submenu is only available when operating via FieldCare, DeviceCare or the SmartBlue app. It contains the wizards that are provided with the Heartbeat Verification and Heartbeat Monitoring application packages. Documentation on the Heartbeat Technology: Endress+Hauser website: www.endress.com → Downloads.
Liquiphant FTL64 HART Diagnostics and troubleshooting 10.5 Proof testing for SIL/WHG devices (optional) The "Proof test" module contains the Proof test wizard, which must be performed at appropriate intervals in the following applications: SIL (IEC61508), WHG (German Water Resources Act (Gesetz zur Ordnung des Wasserhaushalts)): •...
Diagnostics and troubleshooting Liquiphant FTL64 HART Communication via CDI interface not working Possible cause: Wrong setting of the COM port on the computer Remedial action: Check the setting of the COM port on the computer and correct it if necessary...
Liquiphant FTL64 HART Diagnostics and troubleshooting Connection via SmartBlue not possible Possible cause: Incorrect password entered Remedial action: Enter the correct password, paying attention to lower/upper case Connection via SmartBlue not possible Possible cause: Forgotten password Remedial action: Use the operating key on the electronic insert to reset the password or contact Endress+Hauser Service (www.addresses.endress.com)
Page 42
Diagnostics and troubleshooting Liquiphant FTL64 HART Status signals "Failure (F)" option A device error has occurred. The measured value is no longer valid. "Function check (C)" option The device is in the service mode (e.g. during a simulation). "Out of specification (S)" option The device is being operated: •...
Liquiphant FTL64 HART Diagnostics and troubleshooting 11.3 Diagnostic event in the operating tool If there is a diagnostic event in the device, the status signal appears on the top left in the status section of the operating tool together with the associated icon for event behavior according to NAMUR NE 107: •...
Page 44
Diagnostics and troubleshooting Liquiphant FTL64 HART Diagnostic Short text Remedy instructions Status Diagnostic number signal behavior [from the [from the factory] factory] Diagnostic of electronic Electronics faulty 1. Restart device Alarm 2. Replace electronics HART Device Malfunction Check device specific diagnosis.
Liquiphant FTL64 HART Diagnostics and troubleshooting Diagnostic Short text Remedy instructions Status Diagnostic number signal behavior [from the [from the factory] factory] Diagnostic event Deactivate simulation Warning simulation active Configuration Sensor Unit 1. Check sensor configuration Warning invalid 2. Check device configuration...
Diagnostics and troubleshooting Liquiphant FTL64 HART In addition to the operating time when the event occurred, each event is also assigned a symbol that indicates whether the event has occurred or is finished: • Diagnostic event • : Occurrence of the event •...
Liquiphant FTL64 HART Diagnostics and troubleshooting Info number Info name I1513 Download finished I1514 Upload started I1515 Upload finished I1551 Assignment error fixed I1552 Failed: Main electronic verification I1554 Safety sequence started I1555 Safety sequence confirmed I1556 Safety mode off...
Sterilization in Place Repair 13.1 General notes 13.1.1 Repair concept Endress+Hauser repair concept • The devices have a modular design • Customers can carry out repairs For more information on service and spare parts, please contact your Endress+Hauser sales representative. Endress+Hauser...
WARNING Incorrect repair can affect electrical safety! Explosion Hazard! ‣ Only specialist personnel or the Endress+Hauser service team may carry out repairs on Ex-certified devices. ‣ Relevant standards and national regulations on hazardous areas, safety instructions and certificates must be observed.
(WEEE), the product is marked with the depicted symbol in order to minimize the disposal of WEEE as unsorted municipal waste. Do not dispose of products bearing this marking as unsorted municipal waste. Instead, return them to Endress+Hauser for disposal under the applicable conditions.
Liquiphant FTL64 HART Accessories 115 (4.53) 140 (5.51) 32 (1.26) A0038280 28 Protective cover for single compartment housing, aluminum or 316L. Unit of measurement mm (in) 14.4 Plug-in jack The plug-in jacks listed are suitable for use in the temperature range –25 to +70 °C (–13 to +158 °F).
• Weight: 0.54 kg (1.19 lb) • Order number: 52003981 • Order number: 52011891, approval: with inspection certificate EN 10204 - 3.1 material More detailed information and documentation are available: • Product Configurator on the Endress+Hauser website www.endress.com • Endress+Hauser sales organization www.addresses.endress.com 14.6...
Page 53
Liquiphant FTL64 HART Accessories 60 (2.36) 60 (2.36) G 1 A G 1½A (1 NPT) (1½ NPT) A0037667 32 High pressure sliding sleeves. Unit of measurement mm (in) G 1, DIN ISO 228/I • Material: 1.4435 (AISI 316L) • Weight: 1.13 kg (2.49 lb) •...
Technical data Liquiphant FTL64 HART More detailed information and documentation are available: • Product Configurator on the Endress+Hauser website www.endress.com • Endress+Hauser sales organization www.addresses.endress.com Technical data 15.1 Input 15.1.1 Measured variable Level (point level), MAX or MIN safety 15.1.2...
Ex connection data See safety instructions (XA): All data relating to explosion protection are provided in separate Ex documentation and are available from the Downloads Area of the Endress+Hauser-website. The Ex documentation is supplied as standard with all Ex devices. Endress+Hauser...
Technical data Liquiphant FTL64 HART Outdoor operation in strong sunlight: • Mount the device in a shaded location • Avoid direct sunlight, particularly in warmer climatic regions • Use a weather protection cover, can be ordered as an accessory Hazardous area In the hazardous area, the permitted ambient temperature can be limited depending on the zones and gas groups.
Liquiphant FTL64 HART Technical data : standard acceleration of gravity 15.3.9 Mechanical load Support the device in the event of severe dynamic load. Maximum lateral loading capacity of the pipe extensions and sensors: 75 Nm (55 lbf ft). For more details, see the "Supporting the device" section.
• PN: max. 100 bar (1 450 psi) max. 280 °C (536 °F) • With PFA coating (conductive): max. 40 bar (580 psi) max. 230 °C (446 °F) Devices with CRN approval: maximum 90 bar (1 305 psi) for devices with a pipe extension. Information on the Endress+Hauser website: www.endress.com →...