Endress+Hauser Liquiphant FTL62 Operating Instructions Manual

Endress+Hauser Liquiphant FTL62 Operating Instructions Manual

Vibronic hart point level switch with highly corrosion-resistant coating for liquids
Hide thumbs Also See for Liquiphant FTL62:
Table of Contents

Advertisement

Quick Links

BA02214F/00/EN/01.21-00
71548520
2022-02-28
Valid as of version
01.00.zz (Device firmware)
Products
Operating Instructions
Liquiphant FTL62
Vibronic
HART
Point level switch with highly corrosion-resistant coating
for liquids
Solutions
Services

Advertisement

Table of Contents
loading

Summary of Contents for Endress+Hauser Liquiphant FTL62

  • Page 1 Products Solutions Services BA02214F/00/EN/01.21-00 71548520 2022-02-28 Valid as of version 01.00.zz (Device firmware) Operating Instructions Liquiphant FTL62 Vibronic HART Point level switch with highly corrosion-resistant coating for liquids...
  • Page 2 Liquiphant FTL62 HART Order code: XXXXX-XXXXXX Ser. no.: XXXXXXXXXXXX Ext. ord. cd.: XXX.XXXX.XX Serial number www.endress.com/deviceviewer Endress+Hauser Operations App A0023555 Endress+Hauser...
  • Page 3: Table Of Contents

    Liquiphant FTL62 HART Table of contents Table of contents About this document ....6 Electrical connection ....19 Purpose of this document .
  • Page 4 Table of contents Liquiphant FTL62 HART 9.4.2 FieldCare/DeviceCare via service 11.8.2 Resetting the device via operating interface (CDI) ....keys on the electronic insert ..
  • Page 5 Liquiphant FTL62 HART Table of contents 15.4 Process ......56 15.4.1 Process temperature range ..
  • Page 6: About This Document

    About this document Liquiphant FTL62 HART About this document Purpose of this document These Operating Instructions contain all the information that is required in the various phases of the life cycle of the device: from product identification, incoming acceptance and storage, to mounting, connection, operation and commissioning through to troubleshooting, maintenance and disposal.
  • Page 7: Symbols In Graphics

    Registered trademark of the FieldComm Group, Austin, Texas, USA Bluetooth® The Bluetooth® word mark and logos are registered trademarks owned by the Bluetooth SIG, Inc. and any use of such marks by Endress+Hauser is under license. Other trademarks and trade names are those of their respective owners. Apple®...
  • Page 8: Incorrect Use

    It meets the general safety standards and legal requirements. It also complies with the EU directives listed in the device-specific EU Declaration of Conformity. Endress+Hauser confirms this by affixing the CE mark to the device. Endress+Hauser...
  • Page 9: Functional Safety Sil (Optional)

    Liquiphant FTL62 HART Product description Functional Safety SIL (optional) The Functional Safety Manual must be strictly observed for devices that are used in functional safety applications. IT security We only provide a warranty if the device is installed and used as described in the Operating Instructions.
  • Page 10: Product Design

    Incoming acceptance and product identification Liquiphant FTL62 HART Product design A0042276  1 Product design Housing with electronic insert and cover Temperature spacer, pressure-tight feedthrough (second line of defense), optional Process connection flange Pipe extension probe with tuning fork Short pipe probe with tuning fork...
  • Page 11: Product Identification

    All of the information on the measuring device is displayed along with an overview of the scope of technical documentation provided. • Enter the serial number on the nameplate into the Endress+Hauser Operations app or scan the 2-D matrix code on the nameplate with the Endress+Hauser Operations app 4.2.1...
  • Page 12: Mounting

    Mounting Liquiphant FTL62 HART A0042281  2 Handling the device during transportation Mounting Mounting instructions • Any orientation for device with short pipe up to approx. 500 mm (19.7 in) • Vertical orientation from above for device with long pipe •...
  • Page 13: Take Switch Point Into Consideration

    Liquiphant FTL62 HART Mounting A0042298  4 Difference in temperature between outer and inner side of flange Insulation Temperature of flange, outer side Temperature of flange, inner side, for ECTFE maximum 120 °C (248 °F) Temperature difference for ECTFE, PFA maximum 60 °C (140 °F) 5.1.2...
  • Page 14: Take Viscosity Into Consideration

    Mounting Liquiphant FTL62 HART Enamel-coated tuning fork A0043327  6 Typical switch points, enamel-coated tuning fork. Unit of measurement mm (in) Installation from above Installation from below Installation from the side Switch point 5.1.3 Take viscosity into consideration Low viscosity Low viscosity, e.g.
  • Page 15: Avoid Buildup

    Liquiphant FTL62 HART Mounting > 40 (1.57) A0042205  8 Installation example for a highly viscous liquid. Unit of measurement mm (in) 5.1.4 Avoid buildup • Use short installation sockets to ensure that the tuning fork projects freely into the vessel •...
  • Page 16: Support The Device

    Mounting Liquiphant FTL62 HART A0033236  10 Take clearance into consideration 5.1.6 Support the device NOTICE If the device is supported incorrectly, shocks and vibrations can damage the coated surface. ‣ Only use a support in conjunction with ECTFE or PFA plastic coating.
  • Page 17: Installation

    Liquiphant FTL62 HART Mounting 5.2.2 Installation Aligning the tuning fork using the marking The correct alignment allows the medium to flow easily off the tuning fork and prevents the formation of buildup A0042207  12 Markings to align the tuning fork Installing in pipes •...
  • Page 18 Mounting Liquiphant FTL62 HART 2. Turn the housing, align the cable entry.  Avoid moisture in the housing, provide a loop to allow moisture to drain off. 3. Tighten the external locking screw. Turning the housing The housing can be rotated up to 380° by loosening the locking screw.
  • Page 19: Post-Mounting Check

    Liquiphant FTL62 HART Electrical connection 4. Turn the display module to the desired position: maximum 4 × 90 ° in each direction. Insert the display module into the desired position until it clicks into place. Screw the cover tightly back onto the housing. If fitted: tighten the screw of the cover lock using the Allen key 0.7 Nm (0.52 lbf ft) ±0.2 Nm (±0.15 lbf ft).
  • Page 20: Potential Equalization

    Electrical connection Liquiphant FTL62 HART 0.7 Nm A0039520  15 Cover with securing screw 6.2.2 Potential equalization WARNING Explosion Hazard! ‣ Please refer to the separate documentation on applications in hazardous areas for the safety instructions. A0046354 Ground terminal for connecting the potential matching line The protective ground on the device must not be connected.
  • Page 21: Supply Voltage

    6.3.5 Overvoltage protection Devices without optional overvoltage protection Equipment from Endress+Hauser fulfills the requirements of the product standard IEC/DIN EN 61326-1 (Table 2 Industrial Environment). Depending on the type of port (DC supply, input/output port) different test levels according to IEC/DIN EN 61326-1 against transient overvoltages (Surge) are applied...
  • Page 22: Wiring

    Electrical connection Liquiphant FTL62 HART Devices with optional overvoltage protection • Spark-over voltage: min. 400 V • Tested: According to IEC/DIN EN 60079-14 sub chapter 12.3 (IEC/DIN EN 60060-1 chapter 7) • Nominal discharge current: 10 kA Overvoltage category Overvoltage category II...
  • Page 23: Terminal Assignment

    Liquiphant FTL62 HART Electrical connection 6.3.7 Terminal assignment Single compartment housing A0042594  17 Connection terminals and ground terminal in the connection compartment Positive terminal Negative terminal Internal ground terminal Dual-compartment housing, L-shape A0045842  18 Connection terminals and ground terminal in the connection compartment...
  • Page 24: Cable Entries

    Electrical connection Liquiphant FTL62 HART 6.3.8 Cable entries A0045831 Cable entry Dummy plug The type of cable entry depends on the device version ordered. 6.3.9 Available device plugs In the case of devices with a plug, it is not necessary to open the housing for connection purposes.
  • Page 25: Post-Connection Check

    • Operation via optical operating keys on the device display (optional) • Operation via Bluetooth® wireless technology (with optional device display with Bluetooth) with Smartblue app or FieldXpert, DeviceCare • Operation via operating tool (Endress+Hauser FieldCare/DeviceCare, handheld terminal, AMS, PDM, ...) Endress+Hauser...
  • Page 26: To 20 Ma Hart (Fel60H) Electronic Insert

    Operation options Liquiphant FTL62 HART 4 to 20 mA HART (FEL60H) electronic insert Display A0046129  20 Operating keys and DIP switches on the 4 to 20 mA HART electronic insert Operating key for reset password (for Bluetooth login and Maintenance user role) 1+2 Operating keys for device reset (as-delivered state) Operating key for "Proof test"...
  • Page 27: Structure And Function Of The Operating Menu

    Structure and function of the operating menu The differences between the structure of the operating menus of the local display and the Endress+Hauser FieldCare or DeviceCare operating tools can be summarized as follows: The local display is suitable for configuring simple applications.
  • Page 28: Access To The Operating Menu Via The Local Display

    • Press and hold the keys simultaneously to return to the upper level 7.5.2 Operation via Bluetooth® wireless technology (optional) Prerequisite • Device with device display including Bluetooth • Smartphone or tablet with Endress+Hauser SmartBlue app or PC with DeviceCare from version 1.07.05 or FieldXpert SMT70 Endress+Hauser...
  • Page 29: Access To The Operating Menu Via The Operating Tool

    Access via the operating tool is possible: • Via HART communication, e.g. Commubox FXA195 • Via Endress+Hauser Commubox FXA291 With the Commubox FXA291, a CDI connection can be established with the device interface and a Windows PC/notebook with a USB port...
  • Page 30: System Integration

    System integration Liquiphant FTL62 HART System integration Overview of device description files • Manufacturer ID: 17 (0x11) • Device type code: 0x11C4 • Device revision: 1 • HART specification: 7 • DD revision: 1 • Device description files (DTM, DD) information and files at: •...
  • Page 31: System Units

    Liquiphant FTL62 HART Commissioning Device variable Device variable code Terminal current Terminal voltage The device variables can be queried by a HART ® master using HART ® command 9 or 8.2.2 System units The oscillation frequency is specified in Hz. The temperature can be displayed in °C, °F or K.
  • Page 32: Establishing A Connection Via Fieldcare And Devicecare

    A0039148 Computer with FieldCare/DeviceCare operating tool Commubox FXA291 Service interface (CDI) of the device (= Endress+Hauser Common Data Interface) At least 22 mA is required to update (flash) the device firmware. Configuring the device address via software See HART address parameter.
  • Page 33: Setting The Operating Language

    Liquiphant FTL62 HART Commissioning Setting the operating language 9.6.1 Local display Setting the operating language To set the operating language, the display first needs to be unlocked: 1. Press the  key for at least 2 s.  A dialog box appears.
  • Page 34: Device Configuration

    , SmartBlue and on the display, the Commissioning wizard is available to guide the user through the initial commissioning steps. 1. Connect the device to the operating tool. DeviceCare is available for download at www.software-products.endress.com. You must register in the Endress+Hauser software portal to download the product. Endress+Hauser...
  • Page 35: Storing The Oscillation Frequencies

    Liquiphant FTL62 HART Commissioning 2. Open the device in the operating tool.  The dashboard (homepage) of the device is displayed: 3. Open the wizard: Guidance menu → Commissioning wizard 4. Enter the appropriate value in each parameter or select the appropriate option. These values are written directly to the device.
  • Page 36: Locking Or Unlocking The Display Operation

    Commissioning Liquiphant FTL62 HART DIP switch (2) on the electronic insert is used to lock or unlock operation. • If operation is locked via the DIP switch, you can only unlock operation again via the DIP switch. • If operation is locked via the operating menu, you can only unlock operation again via the operating menu.
  • Page 37: Operation

    Liquiphant FTL62 HART Operation Operation 10.1 Reading off the device locking status Displaying active write protection in the Locking status parameter • Local display  : symbol appears on the main page • Operating tool (FieldCare/DeviceCare)  : Navigation: System → Device management → Locking status 10.2...
  • Page 38: Heartbeat Technology (Optional)

    The Heartbeat submenu is only available when operating via FieldCare, DeviceCare or the SmartBlue app. It contains the wizards that are provided with the Heartbeat Verification and Heartbeat Monitoring application packages. Documentation on the Heartbeat Technology: Endress+Hauser website: www.endress.com → Downloads.
  • Page 39: Diagnostics And Troubleshooting

    Liquiphant FTL62 HART Diagnostics and troubleshooting Diagnostics and troubleshooting 11.1 General troubleshooting 11.1.1 General errors Device not responding • Possible cause: Supply voltage does not match the specification on the nameplate Remedial action: Apply the correct voltage • Possible cause: The polarity of the supply voltage is wrong Remedial action: Correct the polarity •...
  • Page 40: Error - Smartblue Operation With Bluetooth

    Diagnostics and troubleshooting Liquiphant FTL62 HART Login via SmartBlue not possible • Possible cause: Device is being put into operation for the first time Remedial action: Enter the user name ("admin") and the password (device serial number) • Possible cause: There is insufficient power available.
  • Page 41: Behavior Of Current Output In The Event Of A Fault

    Liquiphant FTL62 HART Diagnostics and troubleshooting 4. Switch on simulation and check the current output. Replace the main electronics if the current output does not correspond to the simulated value. 11.1.4 Behavior of current output in the event of a fault The behavior of the current output in the event of faults is defined by the Failure behavior current output parameter.
  • Page 42: Diagnostic Event In The Operating Tool

    Diagnostics and troubleshooting Liquiphant FTL62 HART "Maintenance required (M)" option Maintenance required. The measured value remains valid. Diagnostic event and event text The fault can be identified by means of the diagnostic event. The event text helps you by providing information about the fault. In addition, the corresponding status symbol is displayed in front of the diagnostic event.
  • Page 43: Adapting The Diagnostic Information

    Liquiphant FTL62 HART Diagnostics and troubleshooting 11.4 Adapting the diagnostic information The event level can be configured: Navigation: Diagnostics → Diagnostic settings → Configuration 11.5 Queued diagnostic messages The display alternates between the queued diagnostic messages and the measured value.
  • Page 44 Diagnostics and troubleshooting Liquiphant FTL62 HART Diagnostic Short text Remedy instructions Status Diagnostic number signal behavior [from the [from the factory] factory] Main electronics defective Replace main electronics Alarm Data storage inconsistent 1. Restart device Alarm 2. Contact service Memory content 1.
  • Page 45: Event Logbook

    Liquiphant FTL62 HART Diagnostics and troubleshooting Diagnostic Short text Remedy instructions Status Diagnostic number signal behavior [from the [from the factory] factory] Sensor temperature out of 1. Check ambient temperature Warning range 2. Check process temperature Process limit 1. Check process density Alarm 2.
  • Page 46: Overview Of Information Events

    Diagnostics and troubleshooting Liquiphant FTL62 HART • Out of specification (S) • Maintenance required (M) • Information 11.7.3 Overview of information events Info number Info name I1000 --------(Device ok) I1089 Power on I1090 Configuration reset I1091 Configuration changed I11074 Device verification active...
  • Page 47: Resetting The Device Via Operating Keys On The Electronic Insert

    Liquiphant FTL62 HART Maintenance Navigation: System → Device management → Reset device  For details see the "Description of device parameters" documentation. 11.8.2 Resetting the device via operating keys on the electronic insert Display A0046338  26 Operating keys on the electronic insert...
  • Page 48: Repair

    WARNING Incorrect repair can affect electrical safety! Explosion Hazard! ‣ Only specialist personnel or the Endress+Hauser service team may carry out repairs on Ex-certified devices. ‣ Relevant standards and national regulations on hazardous areas, safety instructions and certificates must be observed.
  • Page 49: Historom

    The device must be returned if the wrong device has been ordered or delivered. As an ISO- certified company and also due to legal regulations, Endress+Hauser is obliged to follow certain procedures when handling any returned products that have been in contact with medium.
  • Page 50: Weather Protection Cover For Single Compartment Housing, Aluminum

    Accessories Liquiphant FTL62 HART 229.4 (9.03) 136.7 (5.38) 81 (3.19) 103 (4.06) A0039231  27 Weather protection cover for dual compartment housing. Unit of measurement mm (in) 14.3 Weather protection cover for single compartment housing, aluminum • Material: plastic • Order number: 71438291 115 (4.53)
  • Page 51: Technical Data

    Liquiphant FTL62 HART Technical data ³ (1.57) A0023713  29 Plug-in jack M12 IP69. Unit of measurement mm (in) Plug-in jack M12 IP67 • Elbowed 90 ° • 5 m (16 ft) PVC cable (gray) • Slotted nut Cu Sn/Ni •...
  • Page 52: Signal On Alarm

    Technical data Liquiphant FTL62 HART Continuous operation (FEL60H electronic insert) 4 to 20 mA proportional to the oscillation frequency with superimposed digital communication protocol HART, 2-wire For continuous current output, one of the following modes of operation can be selected: •...
  • Page 53: Switch Output

    Ex connection data See safety instructions (XA): All data relating to explosion protection are provided in separate Ex documentation and are available from the Downloads Area of the Endress+Hauser-website. The Ex documentation is supplied as standard with all Ex devices. 15.2.7...
  • Page 54: Wireless Hart Data

    Technical data Liquiphant FTL62 HART • Sensor temperature • Terminal current The terminal current is the read-back current on terminal block. Visibility depends on order options or device settings • Terminal voltage Visibility depends on order options or device settings Supported functions •...
  • Page 55: Storage Temperature

    Liquiphant FTL62 HART Technical data [°F] [°C] +120 +150 [°C] +194 +248 +302 [°F] A0046544  32 Permitted ambient temperature T at the housing as a function of the process temperature T in the vessel ECTFE-coated PFA- or enamel-coated The following ambient temperature applies over the entire process temperature range for devices with a temperature spacer: +70 °C (+158 °F)
  • Page 56: Vibration Resistance

    Technical data Liquiphant FTL62 HART IP66/IP68 NEMA 4X/6P (1.83 m H O for 24 h) Types of housing: • Single compartment; aluminum, coated; Ex d/XP • Dual-compartment, L-shape; aluminum, 316L; Ex d/XP Degree of protection for M12 plug • When housing is closed and connecting cable is plugged in: IP66/67 NEMA Type 4X •...
  • Page 57: Thermal Shock

    Liquiphant FTL62 HART Technical data 15.4.2 Thermal shock ≤ 120 K/s 15.4.3 Process pressure range WARNING The maximum pressure for the device depends on the lowest-rated element, with regard to pressure, of the selected component. This means that it is necessary to pay attention to the process connection as well as the sensor.
  • Page 58: Viscosity

    Viscosity ≤ 10 000 mPa⋅s 15.4.8 Pressure tightness Up to vacuum In vacuum evaporation plants, select the 0.4 g/cm density setting. 15.4.9 Solids contents ⌀ ≤ 5 mm (0.2 in) 15.5 Additional technical data Current Technical Information: Endress+Hauser website: www.endress.com → Downloads. Endress+Hauser...
  • Page 59: Index

    Liquiphant FTL62 HART Index Index About this document Mounting Symbols - description ..... . . 6 Mounting requirements ....12 Access authorization to parameters Read access .
  • Page 60 *71548520* 71548520 www.addresses.endress.com...