Table 3
Troubleshooting Table
Problem
Water valve won't modulate
Valve opening unstable
Valve opening does not match
input signal
14
Figure 7
Pressure Transducer Graph
140
120
100
80
60
40
20
0
Possible Causes
•
mechanical failure of valve
•
failure of valve actuator
•
incorrect signal sent by 4U1 (ASM) module
•
failure of one or both of the pressure transducers
•
incorrect power supply
•
loose connections
•
noise on signal line
•
potentiometer loose on 4U1 module (tighten set screws)
•
system water pressure incorrect
•
factory settings on valve actuator need to be adjusted
•
incorrect signal
•
improper adjustment to the Zero/Span settings on the valve actuator
•
loose connections
mA
RTHC-SVN02C-EN