Expansion Module Operation; Troubleshooting; Communication; Status Errors - Trane Tracer XM30 Installation, Operation And Maintenance Manual

Expansion module
Table of Contents

Advertisement

Expansion Module Operation

After applying power to the expansion modules, the transmitting (TX) and receiving (RX) LEDs
blink when communication occurs between devices. The following table describes LED activity
and indicators.
Table 9. LED identification and interpretation
LED type
Power
Service
Binary outputs (BO1
through BO8)

Troubleshooting

This section describes possible solutions for communication and status errors that may occur
after the modules have been configured (see
N N o o t t e e : : By clicking the Discover Modules button, you can locate addresses of modules without

Communication

P P r r o o b b l l e e m m :
Points that are referencing expansion modules are in fault or not controlling.
S S o o l l u u t t i i o o n n :
1. Verify that the expansion modules are powered.
2. Visually verify that all modules are communicating (both the TX and RX lights are blinking).
3. In Tracer TU, navigate to the U U t t i i l l i i t t i i e e s s / / C C o o n n t t r r o o l l l l e e r r / / C C o o n n t t r r o o l l l l e e r r S S t t a a t t u u s s screen.
4. In the Expansion Module Status section, confirm that all modules are communicating. After

Status Errors

Error messages that appear in the Tracer TU Expansion Module Status screen are explained
here.
24
LED activity
Solid green
Solid red
Solid green
LED not illuminated
Solid yellow
LED not illuminated
defining them.
clicking S S e e n n d d t t o o D D e e v v i i c c e e , if errors appear in the Errors column see "Status Errors" below.
Indicates...
Normal operation
Low voltage or malfunction
LED has been pressed and
remains on until powered down
Normal operation
Binary output is On/Energized.
Binary output is Off/De-
energized.
"Configuring the Expansion Modules," p.
Troubleshooting/Notes
Sequence on power-up: Illuminates red,
then green.
Sequence on power-up: One short blink
upon power-up or during memory test; will
remain green if memory test fails. When the
service LED is pressed, the module will
continue to use its normal node number for
communication. However, it will communicate
node 0 if possible (this does not affect
operation).
BAS-SVX46E-EN
22).

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tracer xm32Tracer xm70Tracer xm90

Table of Contents