Mitsubishi AJ65BT-D62 User Manual page 73

Table of Contents

Advertisement

9. SELECTING AND EXECUTING THE COUNTER FUNCTION
5) ...... Since the count enable command {RY(n+1)4 (RY(n+1)B} is off, count
operation stops independently of whether the counter function selection start
command {RY(n+1)6 (RY(n+1)D, F.START terminal}.
6) ...... If the count enable command {RY(n+1)4 (RY(n+1)B} is switched on, count
operation remains stopped since the counter function selection start command
{RY(n+1)6 (RY(n+1)D), F.START terminal} is on.
7) ...... Count operation resumes when the counter function selection start command
{RY(n+1)6 (RY(n+1)D), F.START terminal} switches off.
9 - 6