3. SPECIFICATIONS
*1 Master station (RY)
The following is the processing time takes for the remote device station to start
pulse input when the count enable signal {RY(n+1)4 (RY(n+1)B)} is turned on.
[Formula]
SM+LS×1+remote device station processing time(1ms) [ms]
SM: Scan time of master station sequence program
LS : Link scan time
*2 Master station (RWr)
value)
The following is the processing time takes for the master station to read the
counter value counted at the remote station.
[Formula]
SM+LS×1+remote device station processing time(1ms) [ms]
SM: Scan time of master station sequence program
LS : Link scan time
*3 Master station (RX)
The following is the processing time takes for the remote device station to receive
a coincidence signal reset command and for the master station to receive
information that the counter value coincidence (point No. 1) signal {RXn1 (RXn5)}
turned off at the remote station.
* The time takes to transmit the coincidence signal reset command to the remote
station is not included.
[Formula]
SM+LS×1+remote device station processing time(1ms) [ms]
SM: Scan time of master station sequence program
LS : Link scan time
remote device station (RY) processing time (Normal value)
high-speed counter module
remote device station (RWr) processing time (Normal
high-speed counter module
remote device station (RX) processing time (Normal value)
high-speed counter module
3 - 17