4.10.5 SiteTech Software

A personal computer running Kohlerr SiteTecht
software can be used to configure and adjust the RDC
and DC controllers. See TP-6701, SiteTech Software
Operation Manual, for PC connection and software
operation instructions.
See Figure 4-13 for the settings. Refer to TP-6701,
SiteTech Software Operation Manual, for instructions.
Appendix F contains a list of controller parameters that
can be viewed and adjusted using SiteTech.
Access column in the table shows which parameters
can only be viewed (Read or Locked), and which
parameters can be changed using the software (Write).
SiteTech software is also used to update the firmware
on the RDC and DC controllers. See TP-6701 for
instructions.
SiteTech can be used to calibrate the voltage. See
Section 4.11.
SiteTech Group
Genset System Configuration
Genset Info
* With SiteTech versions prior to 2.3, type in CH--740 or CH--1000 with capital letters and dash exactly as shown.
Figure 4-13 Controller Setup Using SiteTech Software
TP-6735 7/17
The
Parameter
Genset System Voltage
Genset System Frequency
Genset Voltage Phase Connection
Engine Model Number
Genset Model Number
Genset Serial Number
Engine Serial number

4.11 Calibration

The controller can be calibrated for utility voltage using
using a personal computer connected to the RDC/DC
controller. Kohlerr SiteTecht software is required for
calibration.
Note: Controller firmware version 2.04 or higher is
required for calibration. See Section 4.10.3 for
instructions to check the firmware version
number.

4.11.1 Calibrate Function

The RDC/DC controller can be calibrated using
SiteTech. Measure the actual utility voltage across L1
and L2, and enter the measured value into SiteTech as
described in the following procedure. See Figure 4-14.
Equivalent
Parameter
Value
Setting
240
230
60
50
Single Phase
Uu01 or Uu06
CH--740*
(14RES or 14RESL)
CH--1000*
(20RES or 20RESL)
14RES
14RESL
20RES
20RESL
See nameplate
See nameplate
RDC
How to Enter
Uu01
Type in
Uu06
Type in
Uu01
Drop-down box
Uu06
Drop-down box
Drop-down box
Type in*
Ec13
Drop-down box
Type in*
Ec14
Drop-down box
none
Type in
none
Type in
none
Type in
Section 4 Controller