Figure 5-6 Continuity Test Results on a Good Stator
(single-phase)
8. If the resistance test proves inconclusive, use a
megohmmeter to test the stator as described in the
next step.
Note: Because
ohmmeter
resistance
readings. Take readings of the rotor and
stator at room temperature.
62
Section 5 Component Testing and Adjustment
Continuity
Yes
No
accuracy
varies,
readings
are
approximate
Note: Make sure that all stator leads are
disconnected
megohmmeter test.
9. Use a megohmmeter to determine whether the
stator is shorted to ground.
a. Apply 500 volts DC to any stator lead and the
stator frame. Perform the megohmmeter test
following the instructions of the megohmmeter
manufacturer.
b. Repeat the test on the other stator leads until
each coil is tested.
Note: A reading of approximately 500 kOhms
(1/2 megohm) and higher indicates a
good stator.
c. Repair or replace the stator if any reading is
less than approximately 500 kOhms.
reading of less than 500 kOhms indicates
deterioration of the winding insulation and
possible current flow to ground.
before
running
the
TP-6735 7/17