Download Print this page

Procedure To Remove Thermistor - Daikin RZQ100KAVLT Service Manual

Hide thumbs Also See for RZQ100KAVLT:

Advertisement

Si281315E

6. Procedure to Remove Thermistor

Procedure
Step
Remove the top panel
and the front panel (2)
and side panel according
to the procedure for
removing outside panels.
1
Pull out the outdoor air
thermistor to the front,
and then slide this
thermistor to the right to
remove it.
Pinch the mounting
2
spring that fixes the
discharge pipe
thermistor to pull out
this thermistor.
Press the fixing section
3
of the suction pipe
thermistor to pull out
this thermistor.
Pull the fixing bracket of
4
the heat exchanger's
distribution pipe
thermistor to the front,
and then remove this
thermistor.
Press the fixing section
5
of the intermediate heat
exchanger thermistor to
pull out this thermistor.
Press the fixing section
6
of the liquid pipe
thermistor to pull out
this thermistor.
Removal Procedure
Warning
Be sure to wait for 10 minutes or more after turning off all power
supplies before disassembling work.
Procedure
Thermistor
Discharge pipe thermistor
(R2T)
Mounting
spring
thermistor
Suction pipe thermistor
(R3T)
Mounting
spring
Thermistor
Liquid pipe thermistor
(R6T)
∗1
The heat exchanger's distribution pipe thermistor,
intermediate heat exchanger thermistor, and liquid pipe
thermistor are jointed together with a single connector.
Consequently, these 3 thermistors should be replaced at
the same time.
Procedure to Remove Thermistor
Points
Thermistor
Outdoor air thermistor
(R1T)
Intermediate heat
exchanger thermistor (R5T)
Heat exchanger distribution
pipe thermistor (R4T)
Thermistor
7

Advertisement

loading

This manual is also suitable for:

Rzq125katltRzq140katlt