Electrical Characteristics - Fujitsu ASUH30LPAS Design & Technical Manual

Wall mounted type
Hide thumbs Also See for ASUH30LPAS:
Table of Contents

Advertisement

10. Electrical characteristics

Model name
Voltage
Power supply
Frequency
1
MCA *
Starting current
MAX. CKT. BKR *
Power cable
Wiring spec.
2
*
Connection
cable *
1
*
: Minimum Circuit Ampacity (Calculation based on UL60335-2-40)
2
*
: Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005. As
the regulations of wire size and circuit breaker differ in each country or region, select appropriate de-
vices complied to the regional standard.
3
*
: Maximum Circuit Breaker
4
*
: Limit voltage drop to less than 2%. If voltage drop is 2% or more, increase cable conductor size.
3
Size
Limited wiring
4
length
AOUH30LPAS1
V
Hz
A
A
13.4
A
AWG
AWG
ft (m)
- 75 -
AOUH36LPAS1
208/230
60
23.4
17.8
30
12
14
167 (51)
10. Electrical characteristics

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Asuh36lpasAouh30lpas1Aouh36lpas1