13) Outdoor temperature zone boundary temperature A
Setting required if changing of the outdoor temperature setting for heat pump prohibition zone is re-
quired when auxiliary heater control by outdoor temperature 1 and 2 are performed on the indoor
unit. For details, refer to "External heater output" in Chapter 8-4.
Function number
66
14) Outdoor temperature zone boundary temperature B
Setting required if changing of the outdoor temperature setting for heat pump only zone is required
when auxiliary heater control by outdoor temperature 1 is performed on the indoor unit. For details,
refer to "External heater output" in Chapter 8-4.
Function number
67
15) Standby time for auxiliary equipment operation
Sets the standby time until the auxiliary equipment operation starts during primary equipment opera-
tion.
For details, refer to Chapter 8-4.
Function number
71
11-1. Function settings by using remote controller
Setting value
00
01
02
03
04
05
06
07
08
"Details of function"
Setting value
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
"Details of function"
Setting value
00
01
02
•
•
•
98
99
- 54 -
"Details of function"
Setting description
-4.0 °F (-20 °C)
-0.4 °F (-18 °C)
3.2 °F (-16 °C)
6.8 °F (-14 °C)
10.4 °F (-12 °C)
14.0°F (-10 °C)
17.6 °F (-8 °C)
21.2 °F (-6 °C)
24.8 °F (-4 °C)
on page 21.
Setting description
42.8 °F (6 °C)
14.0 °F (-10 °C)
17.6 °F (-8 °C)
21.2 °F (-6 °C)
24.8 °F (-4 °C)
28.4°F (-2 °C)
32.0 °F (0 °C)
35.6 °F (2 °C)
39.2 °F (4 °C)
42.8 °F (6 °C)
46.4 °F (8 °C)
50.0 °F (10 °C)
53.6 °F (12 °C)
57.2 °F (14 °C)
60.8 °F (16 °C)
64.4 °F (18 °C)
on page 21.
Setting description
Disable
1 minute
2 minutes
•
•
•
98 minutes
99 minutes
on page 21.
Factory setting
♦
Factory setting
♦
Factory setting
♦
11. Function settings