Omron SYSMAC C200HW-ZW3AT2-E-V2 Operation Manual page 158

Table of Contents

Advertisement

Troubleshooting
Problem
The Controller Link Support Software
is connected to a CV-series PC and
"No unit 0202" is displayed.
A data link table is transferred to a
C200HX/HG/HE Controller Link Unit
and "Comm err 1104" is displayed.
The routing tables are transferred to a
C200HX/HG/HE Controller Link Unit
and "Can't run 2608" is displayed.
Characters are printed abnormally.
Printing is not possible from Windows
95.
The Controller Link Support Software
is being operated under Windows 95
and communications errors such as
"Wrong network" are displayed.
144
Possible cause
The CV-series CPU Unit was
manufactured before April 1996.
Word addresses between CI0 236 and
CIO 299 (words that cannot be
specified) are set in the data link table.
The Routing Table Enabled Bit in the
DM Parameter Area for a
C200HX/HG/HE Controller Link Unit is
set to OFF (disabled).
The correct printer model is not set.
The printer settings are incorrect.
The property settings of the Controller
Link Support Software are incorrect.
Other applications are running in the
background under Windows 95.
Section
Action to be taken
Set routing tables and set the network
address to the value set in the routing
tables (other than 0).
Correct the data link table.
Turn ON the Routing Table Enabled
Bit in the DM parameter area
(enabled).
Check whether the printer model in
the System Setup is correct.
Check the printer settings.
Open the Controller Link Support
Software properties window and
check the Print Screen check box in in
the windows shortcut keys under
"Others" to see if it is selected.
Close other applications running
under Windows 95.
See Appendix D Running Under
Windows 95 for details.