Example 2: if the equation of the output module L2M90 is DEL (00.30 00.30 (AND(L1S1 L1S4)))
after 30 Sec. that the detectors L1S2 and L1S4 are both in alarm the module L2M90 is
-
activated and will remain activated for 30 seconds.
NOTE
if the delay introduced is = 00.00, the equation results active as became active the equation of
delay start and remains active for the time fixed in the lenght
for every equation it is possible to have only one DEL user
if is not specified the lenght time in the Del equation, it will remain activated up to the reset of the
elemts indicated in the equation
the maximum lenght time is 59:59
the maximum time delay value is 10 minuts.
The user "SDEL" is the same of the "DEL" user, with the difference that if during the delay time the equation
becames not true the timing will continue to count to activate the output device.
To restore the timing it is necessary to do an alarm or trouble reset.
Is the user that allow to programm the output activations with periodical time limits.
There are two possible formats:
FORMAT Typo 1 : TIM (SU-MO-TU-WE-TR-FR-SA
Where : 00 = hours, MM = minutes
This format give the possibility to programm weekly limits, for fixed days of the week.
FORMAT Typo 2 : TIM (MM GG AA
Where: MM = month, GG = day, AA =year
This format give the possibility to programm annual limits
Example: IF the equation of the software group G90 is : TIM (SA SU 07.30 13.59)
The group G90 will be activated on Saturday and Sunday from 07.30 a.m. to 13.59pm
NOTE:
if the day, month or year is not indicated, the value takes up the "EACH" meaning
To not specify it is necessary to introduce the " - " sign.
The start date and end date values utilyze the 24 hour format (midnight = 00.00 ... 23.59)
the "00.MM" value as end time has to be greater than the start time
the maximum value for start time and end time is 23:59
Page 38
NOTIFIER ITALIA
SDEL
TIM
Days of activation
(opzional)
OO.MM
Date of activation
(opzional)
Programming manual
Doc. M-145.2-AM1000-ENG Rev A.1
00.MM
00.MM)
start hours
end hours
OO.MM)
start hours
end hours
AM-1000
AM1000_manu