Control Module configured as a Form-C relay, , which will be activated whenever an alarm conditions
APND
occurs. It will be reset via ACK operation.
Control Module configured as a Form-C relay, , which will be activated whenever an alarm conditions
GAC
occurs. It will be reset via RESET operation.
Control Module configured as CON, which will be activated whenever an alarm conditions occurs.
GAS
It will be reset via RESET operation..
Control Module configured as a Form-C relay, , which will be activated whenever an alarm conditions
TPND
occurs. It will be reset via ACK operation.
GTC
Control Module configured as a Form-C relay, , which will be activated whenever a truoble conditions
occurs. It will be reset via RESET operation.
GTS
Control Module configured as CON, which will be activated whenever a trouble conditions occurs.
It will be reset via RESET operation.
Control Module configured as a Form-C relay, , which will be activated whenever a trouble conditions
TRS
occurs. It will be reset via trouble removal only.
HORN
SOUNDER EMA24ALR
% Note. The output modules used for the upon functions do not accept CBE.
INPUT MODULES FOR GENERAL SERVICES
WIRING
Page 22
NOTIFIER ITALIA
Abbrevation
Monitor Module used to monitor line wirw cut or general line
MTRB
Short circuit and trouble.
MACK
Monitor Module used to accomplish remote ACK operation (impulse).
Monitor Module used to accomplish remote SIGNAL SILENCE
MTAC
operation (impulse).
Monitor Module used to accomplish remote RESET
MRES
operation (impulse).
Programming manual
Doc. M-145.2-AM1000-ENG Rev A.1
Type of Device
AM-1000
AM1000_manu