With 56it is possible to select the voice that we want to modify ("Siren " o "Tx Alarm"), the editing function
is activated with the pressure of the return key
The data are introduced with 56and confirmed with the return key
Press the right indicator 4 to modify the audit on the detectors, see the following paragraph:
AUDIT TIME allow the control panel to audit the detector, for a fixed time, before to confirm any alarm.
This function will be activated only with the detectors that are enabled for the audit (see programming Points
menù).
The 56allow the selection of the voice that we want to modify ("Verification " o "Verif. enabled"), the
editing function is activated with the pressure of the return key
The data are introduced with 56and confirmed with the return key
Press the right indicator 4 to modify the parameters for the management of the silence, see the following
paragraph:
TIME FOR THE SILENCE INHIBITION: is the time during which is not admitted the silence operation of the
outputs after an alarm.
AUTORESET TIME: is the time after which the outputs are de-activated.
% Note: the auto-reset function has to be enabled during the single points Programming.
With 56it is possible to select the voice that we want to modify ("Sil. dis." , "Auto Sil." , "Auto Sil. Enab."),
the editing function is activated with the pressure of the return key
The data are introduced with 56and confirmed with the return key
Press the right indicator 4 to modify the parameters for the management of the troubles indications, see the
following paragraph:
TIME FOR THE MAIN TROUBLE DETECTION: is the minimum time therefore the network supply has to
lack to have the Trouble Main signal.
Page 12
NOTIFIER ITALIA
The auti-reset function is enabled by selecting "YES"
Doc. M-145.2-AM1000-ENG Rev A.1
.
.
Programming manual
.
The timing are in seconds
expressed, from a
minimum of 0 to a max of
50 sec.
.
The timing are in seconds
expressed, from a minimum ofi
0 to a max of 255 sec.
The timing are in seconds
expressed, from a minimum of 1
to a max of 2040 sec.
.
.