3.14.3 Setting the Exerciser

This section explains how to change the exercise settings after the initial setup.
Follow the procedure below and see the flowchart in Figure 30 to set the exercise time and date, mode, and frequency.
Procedure to Set the Exerciser
1.
Press the AUTO button on the controller.
2.
Press the Select button to go to the main menu. See the figure titled: VSC Main Menu.
3.
Press the down arrow button to step to the Genset System menu.
4.
Press the Select button to enter the Genset system menu. See the figure titled: Engine Metering Menu.
5.
Use the down arrow button to step to the Next Exercise menu. If the exerciser is not set, No Exercise Scheduled will
be displayed.
6.
Press and HOLD the Select button to enable editing.
7.
Press the Select button. The setting flashes to show that it can be changed. For example, HR fl ashes to show that the
hour can be changed.
8.
Press the Up or Down arrow buttons to change the setting.
9.
Press the Select button to save the setting and move to the next. For example, save HR setting and move to MN.
10. Repeat steps 5 through 9 to change the next item on the line until the desired settings are displayed.
11. Press Select to save after all settings have been selected. Settings will stop flashing.
12. Set the exercise frequency (weekly or every two weeks). Weekly exercises are recommended.
13. Press the down arrow button to step to the Return menu. Press the Select button to return to the main menu.
After a scheduled exercise run, the next exercise time and date will be updated automatically based on the Exercise Frequency
setting.
Exerciser Reset
To reset the exerciser to run at a different day and/or time or to change the exercise mode, follow the procedure in the Setting
the Exerciser section to change the exerciser settings.