Cooling System; Exhaust System - Kohler 6VSG Operation Manual

Dc generator sets
Hide thumbs Also See for 6VSG:
Table of Contents

Advertisement

Paper Element Service
Use the following procedure to replace the paper element at the intervals specified in the service schedule. Replace the pape r
element more often under extremely dusty or dirty conditions.
1.
Press the OFF button on the generator set controller.
2.
Disconnect the AC power to the generator set.
3.
Disconnect the generator set engine starting battery, negative (–) lead first.
4.
Loosen the cover knob and remove the cover.
5.
Remove the element cover nut, element cover, and the paper element with precleaner.
6.
Remove the precleaner from the paper element.
Note:
Do not wash the paper element or clean it with pressurized air, as this will damage the element.
7.
Replace the element if it is dirty, bent, or damaged.
8.
Check the air cleaner base. Make sure it is secure and not bent or damaged. Also check the element cover for damage
and fit. Replace all damaged air cleaner components. Remove any loose dirt or debris from the air cleaner base. Wipe
the base carefully so that no dirt drops into the intake throat. Check the condition of the rubber seal on the air cleaner
stud and replace the seal if necessary.
9.
Reinstall the paper element, precleaner, element cover, element cover nut, and the air cleaner cover. Secure the cover
with the cover knob.
10. Reconnect the AC power to the generator set.
11. Reconnect the generator set engine starting battery, negative (–) lead last.
4.5

Cooling System

The engine fan draws cooling air through the openings in the sides. The alternator fan draws cooling air throu gh an opening on
the side wall of the enclosure. The cooling air mixes with the engine exhaust and is discharged at the exhaust outlet. See th e
service view section for air intake and exhaust locations. To prevent generator set damage caused by overheating , keep the
housing cooling inlets and outlets clean and unobstructed at all times.
Note:
Do not block the generator set cooling air inlets or mount other equipment above them. Overheating and severe generator
damage may occur.
4.6

Exhaust System

Remove all combustible materials from the exhaust location. Combustible materials include building materials as well as natural
surroundings. Keep dry field grass, foliage, and combustible landscaping material a minimum of 1.5 m (5 ft.) from the exhaust
outlet.
Periodically inspect the exhaust system components for cracks, leaks, and corrosion.
Check for corroded or broken metal parts and replace them as needed.
Check that the exhaust outlet is clear.
TP-6843
12/21
59

Advertisement

Table of Contents
loading

Table of Contents