Kohler 6VSG Operation Manual page 26

Dc generator sets
Hide thumbs Also See for 6VSG:
Table of Contents

Advertisement

Warning (W) or
Fault Message
Shutdown (SD)
Engine Oil
SD *
Pressure Low
Fuel Pressure
W
Low
Engine Speed
SD *
High
Exer Not Sch
W
Generator
VoltageL1-L2
SD *
High
Lo Crank Vlt
W
Locked Rotor
SD
MainPwrOverL
SD
Shutdown
Not in Auto
W
Over Crank
SD
Reserve Oil
W
Empty
Speed Sensor
SD
Fault
* Engine cooldown runs before shutting down.
Figure 12
Controller Fault Messages
26
Condition
The LOP switch indicates low oil pressure for more than 5
seconds. Function becomes active 30 seconds after crank
disconnect (30 second inhibit).
Note:
The low oil pressure shutdown does not protect against low
oil level. Check the engine oil level regularly as
recommended in Section 4.
The fuel pressure switch measures low fuel pressure (below
4.5 inches water column). (Optional communications kit
required.)
Engine speed exceeds 115% of the normal running speed for
more than 0.3 seconds.
Exercise not scheduled. No exercise is scheduled on the
controller.
Generator voltage high. Output voltage exceeds 120% of the
system nominal voltage for more than 2 seconds.
Low cranking voltage. Battery voltage falls below 8 VDC for
more than 6 seconds while the starter is engaged.
No engine rotation is sensed during cranking. Shuts down 3
seconds after the fault is detected.
Main power overload. An over current fault on the controller
output (short circuit).
The generator set is not in Automatic (standby) mode.
Remote start and stop commands from a transfer switch or
remote switch will be ignored.
Three unsuccessful starting attempts.
The oil makeup kit reservoir bottle is empty. (Optional
communications kit and oil makeup kit required.)
Engine speed sensing has failed or engine stalled.
Check
Check for leaks in the
lubrication system.
Check the oil level and add oil if
the level is low.
Check fuel supply and fuel
lines.
Contact an authorized
distributor/dealer for service.
See Section 3.6 for instructions
to set the exerciser.
Contact an authorized
distributor/dealer for service.
Charge or replace the battery.
Check the battery.
Check for loose connections.
Contact an authorized
distributor/dealer for service.
Contact an authorized
distributor/dealer for service.
Press AUTO to place the
generator set in Automatic
mode, when appropriate.
Check the fuel supply, spark
plug, and battery.
Check for loose connections.
Contact an authorized
distributor/dealer for service.
Add oil to the oil makeup kit
reservoir.
Contact an authorized
distributor/dealer for service.
TP-6843
12/21