[2-7 Example System with an MA Remote Controller ]

2-7

Example System with an MA Remote Controller

2-7-1

Single Refrigerant System (Automatic Indoor/Outdoor Address Startup)

(1) Sample control wiring
Leave the male
connector on
CN41 as it is.
SW5-1 OFF
OC
00
TB3
TB7
M1 M2
M1 M2
*1. The automatic indoor/outdoor address
setup function is not available when any
HS is connected to a given system.
(2) Cautions
1) ME remote controller and MA remote controller cannot both
be connected to the same group of indoor units.
2) No more than 2 MA remote controllers can be connected to
a group of indoor units.
3) When the number of the connected indoor units is as shown
in the table below, one or more transmission boosters (sold
separately) are required.
To connect two transmission boosters, connect them in par-
allel. (Observe the maximum number of connectable indoor
units that are listed in the specifications for each outdoor
unit.)
When the W/WP/WL200 and
W/WP/WL250 models are not in-
cluded in the connected indoor units
When the W/WP/WL200 and
W/WP/WL250 models are included
in the connected indoor units
The table above shows the number of transmission boost-
ers that is required by the system with four HBCs. For each
HBC added or subtracted, subtract or add two indoor units.
4) Automatic address setup is not available if start-stop input
(CN32, CN51, CN41) is used for a group operation of indoor
units or when multiple indoor units with different functions
BS_02_L
L1
L2
Group
HB
00
TB3
S
M1 M2 S
*1
M1M2
S
TB3
00
Group
HS
A1 B2
A1 B2
MA
Number of transmission booster
(sold separately) required
1 unit
2 units
25 - 50 units
-
19 - 37 units
38 - 50 units
L3
Group
IC
IC
00
00
TB5
TB15
TB5
M1 M2
S
1 2
M1 M2
S
A1 B2
A1 B2
MA
RC
L12
Group
IC
IC
00
00
TB5
TB15
TB5
M1 M2
M1 M2
S
1 2
S
A1 B2
MA
MA
are grouped in the same group. Refer to the following
page(s). [2-7-2 Single Refrigerant System]
(3) Maximum allowable length
1) Indoor/outdoor transmission line
Maximum distance (1.25mm
L1 +L2+L3+L4 200m[656ft]
L1 +L2+L11+L12+L13 200m[656ft]
L1 150m [492ft]
2) Transmission line for centralized control
No connection is required.
3) MA remote controller wiring
Maximum overall line length
2
(0.3 to 1.25mm
m1 200m [656ft]
m2+m3 200m [656ft]
m4+m5 200m [656ft]
*When connecting PAR-31MAA or MA Simple remote
controller, use sheathed cables with a minimum thick-
2
ness of 0.3 mm
Interlock operation with
the ventilation unit
L4
LC
00
TB15
TB5
1 2
M1 M2
S
A1 B2
MA
L13
IC
00
TB15
TB5
TB15
M1 M2
1 2
S
1 2
A1 B2
MA
m3
2
[AWG16] or larger)
[AWG22 to 16])
.
11
chapter 2 -