[8-5 Pressure Sensor Circuit Configuration and Troubleshooting Pressure Sensor Problems ]
8-5-2
High-Pressure Sensor Configuration (Outdoor unit, HBC) (63HS1, PS1, PS3)
The high pressure sensor consists of the circuit shown in the figure below. If DC 5V is applied between the red and the black
wires, voltage corresponding to the pressure between the white and the black wires will be output, and the value of this voltage
will be converted by the microcomputer. The output voltage is 0.071V per 0.098MPa [14psi].
The pressure sensor on the body side is designed to connect to the connector. The connector pin number on the body side
is different from that on the control board side.
Body side
Vcc
Pin 1
Vout
Pin 2
GND
Pin 3
63HS1
Connector
BS_08_L
Control board side
Pin 3
Pin 2
Pin 1
Pressure 0 ~ 4.15 MPa [601psi]
1 2 3
Vout 0.5 ~ 3.5 V
0.071 V / 0.098 MPa [14 psi]
1
GND (Black)
2
Vout (White)
3
Vcc (DC 5 V)(Red)
4.5 [653]
4.0 [580]
3.5 [508]
3.0 [435]
2.5 [363]
2.0 [290]
1.5 [218]
1.0 [145]
0.5 [73]
0
0
0.5
1
1.5
2
2.5
Output voltage (V)
3
3.5
19