[2-7 Example System with an MA Remote Controller ]

2-7

Example System with an MA Remote Controller

2-7-1

Single Refrigerant System (Automatic Indoor/Outdoor Address Startup)

(1) Sample control wiring
L1
Leave the male
Leave the male
connector on
connector on
CN41 as it is.
CN41 as it is.
SW5-1 OFF
SW5-1 OFF
OS2
OS1
00
00
TB3
TB7
TB3
M1 M2
M1 M2
S
M1 M2
(2) Cautions
1) ME remote controller and MA remote controller cannot
both be connected to the same group of indoor units.
2) No more than 2 MA remote controllers can be connected
to a group of indoor units.
3) A transmission booster is required in a system to which
more than 32 indoor units (26 units if one or more indoor
units of the 200 model or above is connected) are con-
nected.
4) Automatic address setup is not available if start-stop in-
put (CN32, CN51, CN41) is used for a group operation of
indoor units or when multiple indoor units with different
functions are grouped in the same group. Refer to the fol-
lowing page(s). [2-7-2 Single Refrigerant System with
Two or More LOSSNAY Units]
5) For information about connecting two or more LOSSNAY
units to a system, refer to the following page(s). [2-7-2
Single Refrigerant System with Two or More LOSSNAY
Units]
12
- chapter 2
L2
Leave the male
Group
connector on
CN41 as it is.
SW5-1 OFF
OC
00
TB3
TB7
TB7
M1 M2
S
M1 M2
M1 M2
S
Group
A B
MA
L3
Group
IC
00
00
TB5
TB15
TB5
M1 M2
S
1 2
M1 M2
S
A B
A B
MA
RC
L12
Group
IC
IC
00
00
TB5
TB15
TB5
M1 M2
S
1 2
M1 M2
S
A B
A B
MA
MA
(3) Maximum allowable length
1) Indoor/outdoor transmission line
Maximum distance (1.25mm
L1 +L2+L3+L4 200m[656ft]
L1 +L2+L11+L12+L13 200m[656ft]
2) Transmission line for centralized control
No connection is required.
3) MA remote controller wiring
Maximum overall line length
2
(0.3 to 1.25mm
[AWG22 to 16])
m1 200m [656ft]
m2+m3 200m [656ft]
m4+m5 200m [656ft]
*When connecting PAR-31MAA or MA remote controller,
use sheathed cables with a minimum thickness of 0.3
2
mm
.
Interlock operation with
the ventilation unit
L4
LC
IC
00
TB15
TB5
1 2
M1 M2
S
A B
MA
L13
IC
00
TB15
TB5
TB15
1 2
M1 M2
S
1 2
A B
MA
m3
2
[AWG16] or larger)
BS_02_M