Trane RTAF-SVX001K-EN Manual page 89

Sintesis air-cooled chillers
Table of Contents

Advertisement

Table 33. Main processor diagnostics (continued)
Diagnostic Name
Low Oil Flow - xy
Low Refrigerant Temperature
Low Suction Refrigerant Pressure
Low Suction Rfgt Pressure
Low Suction Rfgt Pressure
Mfr Maintenance Recommended - xy
Maint Recommended xy
MP: Invalid Configuration
MP: Reset Has Occurred
No Differential Refrigerant Pressure - xy
No Differential Rfgt Pressure - xy
No Diff Rfgt Press - xy
Oil Flow Protection Fault xy
Oil Pressure Sensor - xy
Oil Temperature Sensor - xy
Oil Temp Sensor - xy
Outdoor Air Temperature Sensor
Outdoor Air Temp Sensor
RTAF-SVX001K-EN
Affects
Severity Persistence
Target
Cprsr
Immediate
Latch
Circuit
Immediate
Latch
Circuit
Immediate
Latch
Cprsr
Info
Latch
Platform Immediate
Latch
None
Info
Latch
Cprsr
Immediate
Latch
Cprsr
Immediate
Latch
Cprsr
Immediate
Latch
Cprsr
Normal
Latch
Chiller
Normal
Latch
Active
Modes
[Inactive
Modes]
The intermediate oil pressure sensor for
this compressor was out of the acceptable
Cprsr
pressure range for 15 seconds, while the
Energized and
Delta Pressure was greater than 15 Psid
Delta P above
(172.4 kPa).: Acceptable range is 0.50 >
15 Psid
(PC-PI) / (PC-PE) for the first 2.5 minutes
of operation, and 0.28 > (PC-PI) / (PC-PE)
thereafter.
The respective Evaporator Refrigerant Pool
Temperature dropped below the Low
Refrigerant Temperature Cutout Setpoint
for 2250°F-sec (12°F-sec max rate for
early circuit startup period) while the
All Ckt Running
circuit was running. The minimum LRTC
Modes
setpoint is -5°F (18.7 Psia) the point at
which oil separates from the refrigerant.
The integral is held nonvolatile though
power down, is continuously calculated,
and can decay or build during the circuit off
cycle as conditions warrant.
a. The Suction Pressure dropped below 10
Psia just prior to compressor start (after
EXV preposition). b. During Early Startup
Period: the Suction Pressure fell below a
pressure equal to Condenser Pressure ÷ 8
but as limited to not less than 6 or greater
Cprsr Prestart
than10 psia. c. After Early Startup Period
and Cprsr
expires: The Suction Pressure fell below 16
Energized
Psia.
(Note: the Early Startup Period is between
1 and 5 min as an inverse function of the
Cond Temp measured at time of circuit
startup).
Service
Compressor service recommended as
Messages
service interval hours have elapsed.
Enabled
MP has an invalid configuration based on
All
the current software installed.
The main processor has successfully come
out of a reset and built its application. A
reset may have been due to a power up,
installing new software or configuration.
All
This diagnostic is immediately and
automatically cleared and thus can only be
seen in the Historic Diagnostic List in
Tracer TU.
The system differential pressure was
below 7.7 Psid (53 kPa) for 6 seconds after
Compressor
the 11 seconds ignore time relative to
running on
cprsr/circuit startup had expired. In a two
Circuit
compressor circuit, the lower of the two
suction pressures is used for DP.
The Intermediate Oil Pressure Sensor for
Starter
this cprsr is reading a pressure either
Contactor
above its respective circuit's Condenser
Energized [all
Pressure by 15 Psia or more, or below its
Stop modes]
respective Suction Pressure 10 Psia or
more for 30 seconds continuously.
All
Bad Sensor or LLID
All
Bad Sensor or LLID
All
Bad Sensor or LLID.
Diagnostics
Reset
Criteria
Level
Local
Remote
Local
Remote
Remote
Remote
Remote
Local
Remote
Remote
Remote
89