Table 33. Main processor diagnostics (continued)
Diagnostic Name
Excessive Condenser Pressure
External Chilled Water Setpoint
Ext Chilled Wtr Setpt
External Demand Limit Setpoint
Ext Demand Limit Setpoint
EXV Pressure Equalization Failed
EXV Press Equalization Fail
Free Cooling Entering Water
Temperature
FC Entering Water Temp
Heat Recovery Entering Water
Temperature Sensor
Heat Recovery Entering Water Temp
Sensor
Heat Rcvry Ent Water Temp
Heat Recovery Leaving Water
Temperature Sensor
Heat Recovery Leaving Water Temp
Sensor
Heat Rcvry Leav Water Temp
High Compressor Refrigerant Discharge
Temp - xy
High Cprsr Rfgt Discharge Temp - xy
High Cprsr Disch Temp xy
High Differential Refrigerant
Pressure - xy
High Differential Rfgt Pressure - xy
High Diff Rfgt Pressure - xy
High Evaporator Refrigerant Pressure
High Evap Rfgt Pressure
RTAF-SVX001K-EN
Affects
Severity Persistence
Target
Circuit
Immediate
Latch
Chiller
Info
Latch
Chiller
Info
Latch
Circuit
Immediate
Latch
Free
Normal
Latch
Cooling
Chiller
Info
Latch
Chiller
Info
Latch
Cprsr
Immediate
Latch
Cprsr
Normal
Latch
Chiller
Immediate
NonLatch
Active
Modes
[Inactive
Modes]
The condenser pressure sensor of this
circuit has detected a condensing pressure
All
in excess of the design high side pressure
as limited by the particular compressor
type.
a. Function Not "Enabled": no diagnostics.
b. "Enabled ": Out-Of-Range Low or Hi or
All
bad LLID, set diagnostic, default CWS to
next level of priority (e.g. Front Panel
SetPoint).
a. Not "Enabled": no diagnostics. b.
"Enabled ": Out-Of-Range Low or Hi or bad
All
LLID, set diagnostic, default CLS to next
level of priority (e.g. Front Panel SetPoint.)
EXV Pressure Equalization process failed
All
to meet the equalization criteria within the
allotted time.
All
Bad Sensor or LLID
All
Bad Sensor or LLID
All
Bad Sensor or LLID
The compressor discharge temperature
exceeded 199.4?F (without oil cooler) or
230ºF (with oil cooler). This diagnostic will
All
be suppressed during Stopping mode or
[compressor
after the compressor has stopped. Note:
run unload or
As part of the Compressor High
compressor not
Temperature Limit Mode (aka Minimum
running]
Capacity Limit), the compressor shall be
forced loaded as the filtered discharge
temperature reaches 190ºF (without oil
coolers), or 220ºF (with oil coolers).
GP2 Cprsr: The differential pressure for
the respective circuit was above 275 Psid
Cprsr
Energized
(1890 kPa) for 2 consecutive samples 5
seconds apart.
The evaporator refrigerant pressure of
either circuit has risen above 190 psig. The
evaporator water pump relay will be de-
energized to stop the pump regardless of
why the pump is running. The diagnostic
will auto reset and the pump will return to
normal control when all of the evaporator
All
pressures fall below 185 psig. The primary
purpose is to stop the evaporator water
pump and its associated pump heat from
causing refrigerant side pressures, close to
the evaporator relief valve setting, when
the chiller is not running, such as could
occur with Evap Water Flow Overdue or
Evaporator Water Flow Loss Diagnostics.
Diagnostics
Reset
Criteria
Level
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
85