Trane RTAF-SVX001K-EN Manual page 51

Sintesis air-cooled chillers
Table of Contents

Advertisement

AFD Drive Programming
Field replacement drives must be programmed via the
keypad interface. Program parameters sequentially by ID
values as defined in tables below.
Table 24. Non-compressor specific parameter settings
ID
Description
0-03
Region Settings
0-20
Display Line 1.1 Small
0-24
Display Line 3 Large
0-40
[Hand on] Key on LCP
0-41
[Off] Key on LCP
0-60
Main Menu Password
0-61
Access to Main Menu w/o Password
1-03
Torque Characteristics
1-21
Motor Power [HP]
1-22
Motor Voltage
1-23
Motor Frequency
1-24
Motor Current
1-25
Motor Nominal Speed
1-71
Start Delay
1-73
Flying Start
1-78
Compressor Start Max Speed [Hz]
1-79
Compressor Start Max Time to Trip
1-82 Min Speed for Function at Stop [Hz]
1-87
Trip Speed Low [Hz]
3-02
Minimum Reference
(b)
3-03
Minimum Reference
3-41
Ramp 1 Ramp Up Time
3-42
Ramp 1 Ramp Down Time
3-82
Starting Ramp Up Time
4-10
Motor Speed Direction
4-12
Motor Speed Low Limit [Hz]
4-18
Current Limit
Table 25. Compressor-specific parameter settings, 115 to 215 tons — 60Hz
Parameters
ID
Description
460V 380V 575V 460V 380V 575V 460V 380V 575V 460V 380V 575V 460V 380V 575V
1-21 Motor Power (hp)
86
1-22 Motor Voltage (V) 460V
1-24 Motor Current (A)
91A
Motor Nominal
1-25
3461
Speed (rpm)
Max Output
4-19
61
Frequency (Hz)
Voltage at Main
14-11
391V
Fault (V)
(a) 400V/50 Hz units use 380V/60Hz compressor settings.
RTAF-SVX001K-EN
Setting
[1] North American
[1612] Motor Voltage
[1617] Speed (rpm)
[0] Disabled
[0] Disabled
999
[1] LCP: Read-only
[0] Compressor Torque
(a)
See table below
See table
below(a)
60Hz
See table
below(a)
See table
below(a)
0s
[0] Disabled
30Hz
10s
10Hz
25Hz
30Hz
See
Table 26
5s
5s
3s
[0] Clockwise
30Hz
128.4%
L1
L2
86
86
102
102
380V
575V
460V
380V
110A
73A
109A
132A
3460
3461
3459
3466
61
61
61
61
323V
489V
391V
323V
Table 24. Non-compressor specific parameter settings
(continued)
ID
Description
4-19
Max Output Frequency
4-
Motor Speed High Limit [Hz]
14(b)
5-12
Terminal 27 Digital Input
5-13
Terminal 29 Digital Input
5-40.0
Function Relay 1
5-40.1
Function Relay 2
5-41.0
On Delay, Relay 1
5-41.1
On Delay, Relay 2
5-42.0
Off Delay, Relay 1
5-42.1
Off Delay, Relay 2
6-10
Terminal 53 Low Voltage
6-14
Terminal 53 Low Ref./Feedb. Value
6-
Terminal 53 High Ref./Feedb. Value
15(b)
6-50
Terminal 42 Output
14-03
Overmodulation
14-10
Mains Failure
14-11
Mains Voltage at Mains Fault
14-20
Reset Mode
14-30 Current Lim Ctrl. Proportional Gain
14-31
Current Lim Ctrl. Integration Time
14-50
RFI Filter
14-51
DC Link Compensation
22-75
Short Cycle Protection
22-76
Interval Between Starts
(a) For unit sizes 115 to 215, see
see
Table
26.
(b) Parameter for 230 to 520 ton units only.
(a)
M3
102
122
122
122
575V
460V
380V
575V
87A
128A
154A
101A
3461
3502
3505
3503
61
61
61
61
489V
391V
323V
489V
Installation Electrical
Setting
See table
See
[2] Coast Inverse
[0] No Operation
[5] Running
[3] Drive Rdy/Rem Ctrl
See
[133] Motor Cur. 4-
[0] Off
[4] Kinetic Back-up
See table
[1] Automatic Reset x 1
[0] Off
[1] On
[1] Enabled
Table
25. For unit sizes 230 to 520 tons,
M4
144
144
144
177
460V
380V
575V
460V
151A
182A
120A
183A
3494
3494
3494
3494
61
61
61
61
391V
323V
489V
391V
below(a)
Table 26
1s
1s
1s
1s
2V
30Hz
Table 26
20mA
below(a)
25%
1s
60s
N3
177
177
380V
575V
221A
146A
3495
3493
61
61
323V
489V
51