Table 32. Starter diagnostics (continued)
Diagnostic Name and
Source
Transition Complete Input
Shorted - xy
(Trnsn Compl Input Short xy)
Under Voltage
RTAF-SVX001K-EN
Affects
Severity Persistence
Target
Cprsr
Immediate
Latch
Chiller
Normal
NonLatch
Active
Modes
[Inactive
Modes]
The Transition Complete input was found to be
Pre-Start
shorted before the compressor was started. This
is active for all electromechanical starters.
Pre-Start and
Nom. trip: 60 seconds at less than 87.5%, ? 2.8%
Any Ckt(s)
at 200V ? 1.8% at 575V, Auto Reset at 90% or
Energzd
greater for 10 cont secs.
Diagnostics
Criteria
Reset