BLOWER DATA
BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT WITH WET INDOOR COIL & AIR FILTERS IN PLACE.
FOR ALL UNITS ADD:
1 − Any factory installed options air resistance (electric heat, economizer, etc.). See table below
2 − Any field installed accessories air resistance (duct resistance, diffuser, etc.). See page 17
Then determine from table the blower motor output and drive required.
0.30 to 1.30 in. w.g.
Air
Volume
cfm
0.30
0.40
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Furnished
5600
609
1.51
652 1.71
6000
630
1.75
670 1.95
6500
650
2.05
690 2.28
7000
675
2.35
715 2.63
7500
700
2.75
738 3.03
8000
725
3.20
763 3.50
8400
746
3.55
783 3.87
NOTE − Bold − To operate in this range, unit must be ordered with High Static Drive and drive kit #7 must be ordered separately for field installation.
1.40 to 2.50 in. w.g.
Air
Volume
cfm
1.40
1.50
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Static − 5 HP, Drive Kit 3
5600
985 3.74 1012 3.95 1037 4.15 1062 4.35 1087 4.58 1112 4.80 1135 5.00 1157 5.20 1180 5.41 1202 5.62 1223 5.83 1244 6.04
6000
998 4.13 1025 4.35 1050 4.58 1075 4.80 1098 5.00 1120 5.20 1145 5.43 1170 5.65 1193 5.88 1215 6.10 1235 6.33 1255 6.55
6500
1013 4.63 1040 4.85 1065 5.10 1090 5.35 1115 5.60 1140 5.85 1163 6.08 1185 6.30 1205 6.53 1225 6.75 1248 7.00 1270 7.25
7000
1030 5.18 1055 5.40 1080 5.68 1105 5.95 1130 6.20 1155 6.45 1178 6.70 1200 6.95 1220 7.20 1240 7.45 1263 7.73 1285 8.00
7500
1048 5.78 1075 6.05 1100 6.33 1125 6.60 1148 6.88 1170 7.15 1193 7.40 1215 7.65 1238 7.95 1260 8.25 1280 8.50 1300 8.75
8000
1065 6.40 1090 6.70 1115 6.98 1140 7.25 1163 7.55 1185 7.85 1208 8.13 1230 8.40 1253 8.70 1275 9.00 1295 9.30 1315 9.60
8400
1081 6.96 1106 7.26 1131 7.58 1156 7.89 1179 8.19 1201 8.49 1224 8.79 1246 9.09 1266 9.38 1286 9.67 1307 9.98 1328 10.29
NOTE − Bold, italics − drive is capable of the values noted but will exceed motor horsepower.
Italics − field furnished drive
AIR RESISTANCE (in. w.g.) − Factory Installed Options
Air Volume − cfm
5600
6000
6500
7000
7500
8000
8400
External Static (in. w.g.) Covered By Drive At Nominal Air
With Economizer, Standard Filters And Wet Indoor Coil
0.50
0.60
0.70
Low Static − 5 HP, Drive Kit 2
694 1.91
732
2.12
769 2.33
710 2.15
748
2.38
785 2.60
730 2.50
768
2.75
805 3.00
755 2.90
790
3.15
825 3.40
775 3.30
810
3.58
845 3.85
800 3.80
833
4.08
865 4.35
819 4.18
853
4.49
886 4.80
External Static (in. w.g.) Covered By Drive At Nominal Air
With Economizer, Standard Filters And Wet Indoor Coil
1.60
1.70
1.80
High Static − 7.5 HP, Drive Kit 6
Electric Heat
Economizer
− − −
.01
.01
.01
.01
.02
.02
0.80
0.90
Standard Static − 5 HP, Drive Kit 3
803 2.53
837 2.73
868 2.93
818 2.83
850 3.05
880 3.25
838 3.23
870 3.45
900 3.70
858 3.68
890 3.95
920 4.20
878 4.15
910 4.45
938 4.70
898 4.65
930 4.95
958 5.23
916 5.12
946 5.43
974 5.73 1001 6.03 1029 6.35 1056 6.66
1.90
2.00
2.10
Horizontal
Roof Curb
− − −
− − −
.02
.04
.06
.09
.11
Page 5
1.00
1.10
1.20
899 3.13
928 3.33
910 3.45
940 3.68
930 3.95
958 4.18
950 4.45
978 4.70 1005 4.95
965 4.95
993 5.23 1020 5.50
985 5.50 1013 5.80 1040 6.10
2.20
2.30
2.40
MERV 11
Filter
.10
.02
.11
.02
.13
.02
.15
.03
.17
.03
.19
.04
.21
.04
17.5 TON
TCA210
1.30
957
3.53
970
3.90
985
4.40
TCA210
2.50