BLOWER DATA

BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT WITH WET INDOOR COIL & AIR FILTERS IN PLACE.
FOR ALL UNITS ADD:
1 − Any factory installed options air resistance (electric heat, economizer, etc.). See table below
2 − Any field installed accessories air resistance (duct resistance, diffuser, etc.). See page 17
Then determine from table the blower motor output and drive required.
0.40 to 1.50 in. w.g.
Air
Volume
0.40
0.50
cfm
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Low Static − 3 HP, Drive Kit A
4800
577 1.13 620 1.31 662 1.48 702 1.66 742 1.83 777 2.01 811 2.18 842 2.36 872 2.54 902 2.72 932 2.89 960 3.07
5000
585 1.25 628 1.43 670 1.60 710 1.78 750 1.95 783 2.13 815 2.30 848 2.50 880 2.70 910 2.88 940 3.05 968 3.23
5500
605 1.45 648 1.65 690 1.85 728 2.05 765 2.25 800 2.45 835 2.65 865 2.85 895 3.05 925 3.25 955 3.45 983 3.65
6000
630 1.75 670 1.95 710 2.15 748 2.38 785 2.60 818 2.83 850 3.05 880 3.25 910 3.45 940 3.68 970 3.90 998 4.13
6500
650 2.05 690 2.28 730 2.50 768 2.75 805 3.00 838 3.23 870 3.45 900 3.70 930 3.95 958 4.18 985 4.40 1013 4.63
7000
675 2.35 715 2.63 755 2.90 790 3.15 825 3.40 858 3.68 890 3.95 920 4.20 950 4.45 978 4.70 1005 4.95 1030 5.18
7200
687 2.55 725 2.81 763 3.06 798 3.33 833 3.60 866 3.86 898 4.11 926 4.36 954 4.61 984 4.90 1013 5.19 1038 5.44
NOTE − Bold − To operate in this range, unit must be ordered with High Static Drive and drive kit #3 must be ordered separately for field installation.
1.60 to 2.60 in. w.g.
Air
Volume
1.60
1.70
cfm
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
High Static − 5 HP, Drive Kit 4
4800
987 3.24 1014 3.42 1041 3.60 1064 3.78 1087 3.95 1112 4.13 1136 4.30 1159 4.50 1181 4.70 1204 4.88 1226 5.06
5000
995 3.40 1020 3.60 1045 3.80 1070 3.98 1095 4.15 1118 4.33 1140 4.50 1163 4.70 1185 4.90 1208 5.10 1230 5.30
5500
1010 3.85 1035 4.05 1060 4.25 1085 4.48 1110 4.70 1133 4.90 1155 5.10 1178 5.30 1200 5.50 1220 5.70 1240 5.90
6000
1025 4.35 1050 4.58 1075 4.80 1098 5.00 1120 5.20 1145 5.43 1170 5.65 1193 5.88 1215 6.10 1235 6.33 1255 6.55
6500
1040 4.85 1065 5.10 1090 5.35 1115 5.60 1140 5.85 1163 6.08 1185 6.30 1205 6.53 1225 6.75 1248 7.00 1270 7.25
7000
1055 5.40 1080 5.68 1105 5.95 1130 6.20 1155 6.45 1178 6.70 1200 6.95 1220 7.20 1240 7.45 1263 7.73 1285 8.00
7200
1063 5.68 1088 5.94 1113 6.19 1136 6.44 1159 6.69 1182 6.96 1204 7.23 1226 7.50 1248 7.77 1269 8.03 1289 8.28
NOTE − Bold, italics − drive is capable of the values noted but will exceed motor horsepower.
AIR RESISTANCE (in. w.g.) − Factory or Field Installed Options
Air Volume − cfm
4800
5000
5500
6000
6500
7000
7200
0.60
0.70
0.80
Standard Static − 3 HP, Drive Kit 1
1.80
1.90
2.00
Electric Heat
Economizer
− − −
− − −
− − −
.01
.01
.01
.01
External Static (in. w.g.)
0.90
1.00
1.10
External Static (in. w.g.)
2.10
2.20
Horizontal
Roof Curb
− − −
− − −
− − −
− − −
.02
.04
.05
Page 4
1.20
1.30
1.40
2.30
2.40
2.50
Field Furnished Drive
MERV 11
Filter
.08
.01
.08
.01
.10
.02
.11
.02
.13
.02
.15
.03
.16
.03
15 TON
TCA180
1.50
TCA180
2.60